Info!
The set
scale is displayed only on home screen when temperature is set between 40>60°C.
IR
So when you see
scale, you know that
in operation and heating according to set scale.
IR
IR is
If Set
scale
not displayed, you know that
is completely shut off.
IR
IR
is
IR in Operation
IR completely shut off
IR during Standby operation:
IR
IR
operation is not allowed during standby operation.
can only be used with bath.
During standby operation only sauna heater is preheated. Then when bath is started thru
control panel Elite or external switch, the
heater will start. Note!
only start if set
IR
IR
temperature is between 40>60°C and set
scale is between 1>10.
IR
Forced preheating:
F
IR
IR
orced preheating in 20min of
starts when
operation is activated
time during
first
ongoing bath. Forced preheating is dependent on R
temp in room vs set temp. Forced
eal-
preheating is only allowed to start once during a bath.
F
IR
orced preheating of
is never given when R
-temp in room is the same as set temp or
eal
higher during operation.
Interlock when to high temperature in room:
If the
temperature in room reaches 68°C during ongoing bath when
is in operation (set
Real-
IR
temperature between 40>60°C) then
operation is paused automatically until temperature
IR
drops down to at least 67°C then
starts again. This function works hidden in the system, no
,
IR
notice is displayed when the pause occur.