The inverter will automatically shut off under a short circuit fault. The CPU is designed to
detect short circuits and in order to avoid unnecessary tripping of the reserve (utility
supply) breaker, the static switch will remain open or inactive. (There will be no output
power present)
Listed below are all the warning conditions that can be displayed (they are arranged in
order of priority, starting with the highest priority):
1
st
row:
BYPASS ON
– Output is being supplied by the reserve
RECT AC FAIL
– AC utility source failure
RECTIFIER PHASE ERROR
– AC utility phase loss or one phase out of
operating parameters
RESERVE FREQ. ERROR
– AC utility frequency is out of parameters and
reserve has been disabled until error is corrected
2
nd
row:
170% OVERLOAD
– over 170% maximum capacity for the ELI system.
150% OVERLOAD
– over 150% maximum capacity for the ELI system.
125% OVERLOAD
– over 125% maximum capacity for the ELI system.
110% OVERLOAD
– over 110% maximum capacity for the ELI system.
3
rd
row:
BATTERY LOW STOP
– Battery have been exhausted.
BATTERY LOW
– Batteries have passed the low voltage level and will soon
be exhausted.
BATTERY BAD
– One or more cells have tested faulty.
BATTERY GND FAULT
– Battery cabinet not grounded properly.
BATTERY TESTING
– performing test on the batteries.
Listed below are all the fault conditions that can be displayed:
1
st
row:
2
nd
row:
HIGH DC SHUTDOWN
– DC Bus voltage out of operating range.
SHORT CIRCUIT!
– a short circuit condition has occurred on the output.
FUSE/OVERHEAT –
a fuse has blown or the system has shutdown due to
overheating.
OVERLOAD SHUTDOWN
– system has exceeded the overload limit beyond
the operating window.
EMERGENCY STOP –
user has activated the emergency stop feature.
INVERTER ABNORMAL –
inverter is not operating within specified
parameters.
3
rd
row:
mode.
BYPASS ON SHUTDOWN
– inverter failure, system operating in bypass
The UP (
↑
) or DOWN (
↓
) key has no function in this menu. The screen will go back to
MENU 1, when ENTER (
↵
) is pressed.