STEP 14:
Make sure lid gasket is clean and free from any particles,
then carefully close the cover, making sure that wires are clear of the
seam and hinge area. Use the special key to close the two cover locks.
Auxiliary Output Wiring
TECH CORNER
Additional Information you may find useful
1.
CONTROLLER:
The controller turns off power to the load at 22V and
reconnects when the battery reaches 24V. This protects battery from
overdischarge and increases battery life and performance.
2.
CAPACITY:
The UPSPro UPS-ST2424-UBNT is rated at up to 30W
power output. If you exceed this load the system may not function to
expectations.
3.
VENTING:
The enclosure is vented thru the wire feedthrus and vari-
ous hole plugs in the bottom of the enclosure. Don’t make these airtight
with silicon
4.
BATTERY MAINTENANCE:
The batteries used in the UPSPro sys-
tems don’t require any maintenance. They should last up to 5 years in
normal use.
5.
BATTERY OVERDISCHARGE
: We highly recommend hooking all
equipment loads to the controller voltage output. This output will discon-
nect the load if the battery voltage drops below 22V and this will protect
the battery from over-discharge. If batteries get completely discharged
because the equipment was connected directly to the battery, you will
reduce the battery life and you will most likely need to supercharge
Device 1
Device 2
FG
= Frame Ground (Do Not Connect to
V-)
GND
= V- (There are two V– connec-
tions:1 and 2)
+12V or +24V
= V+ (There are two V+
connections: 1 and 2)
+
-