STEP 11:

  When  a battery is connected properly the BATT LED will be 

green.  Make sure that the Battery Type is selected correctly and never 

change the battery type during charging or this could damage the con-

troller. Use GEL for GEL or AGM batteries. Use WET for standard lead 

acid wet cells. Tycon recommends using only GEL or AGM batteries for 

best performance.

 

The controller has battery overdischarge protection to disconnect the 

load if the battery voltage (charge) is too low. The LOAD LED will be on 

when the battery charge is within safe limits and the LOAD output is 

turned on.

 

 

STEP 12:

  Switch off controller and connect AC to the controller. Be 

sure to follow local regulations for  outdoor 120/240VAC connections. 

 

STEP 13:

  Connect the load to the controller LOAD terminals. Be sure 

to observe proper polarity. Switch on the controller to activate the 

charging.

 

STEP 14:

  Plug or Tighten all wire feedthrus. If they don

t tighten on a 

small diameter wire, you can wrap some electrical tape around the wire 

in the seal area to increase its diameter and make a better seal. The 

enclosure needs some small amount of venting so be sure NOT to seal 

all holes and feedthrus with silicon. 

 

STEP 15:

  Make sure lid gasket is clean and free from any particles, 

then carefully close the cover, making sure that wires are clear of the 

seam and hinge area. Use the special key to close the two cover locks.

 

 

TECH CORNER

 

 

Additional Information you may find useful

 

1.

 CONTROLLER: 

The  controller  turns  off  power  to  the  load  at  10.7V 

for  the  12V  model  and  21.5  for  the  24V  model  and  40V  for  the  48V 

model. It reconnects when the battery reaches 12.6V for the 12V model 

and 25.2V for the 24V model and 51V for the 48V model. This protects 

battery from overdischarge and increases battery life and performance. 

Note:  The  load  will  turn  on  immediately  as  soon  as  AC  power  is  re-

stored. 

 

2.

 

CAPACITY: 

The UPSPro  UPS

-

ST12 is rated at 120W load output. 

The UPS

-

ST24 and UPS

-

ST48 are also rated at 120W load output. 

 

LED Indicators 

 

LOAD 

(Load Power is Turned On = Green) 

 

PWR 

(AC Power On = Yellow) 

 

BATT 

( Battery is Connected = Green) 

 

CHD 

( Battery is Fully Charged = Green) 

 

CHG ( Battery is Charging = Yellow) 

 

WET / GEL 

 

Switch is positioned to WET(Green) or GEL

(Yellow) 

 

Содержание UPS-ST12

Страница 1: ...power circuits Contact with power lines lights or power circuits may be fatal We rec ommend to install no closer than 20 feet to any power lines Safety For your own protection follow these safety rules Perform as many functions as possible on the ground Do not attempt to install on a rainy windy or snowy day or if there is ice or snow accumulation at the install site or if the site is wet Make sur...

Страница 2: ...us into the bottom connector plate Attach the connector plate to the bottom of the enclosure using self tapping screws provided STEP 3 Install hole plug in drain hole in bottom right corner of the en closure STEP 4 If pole mounting the enclosure assemble the pole mount kit to the back of the enclosure and mount the enclosure to a pole using the 6 hose clamps provided The enclosure can also be wall...

Страница 3: ...e batteries in the enclosure If using multiple batter ies connect in parallel for 12V output or connect in series for 24V out put 12V 200Ah battery configuration is shown here For 12V 100Ah two batteries are connected in parallel with Plus connected to Plus and Minus con nected to Minus For 12V 200Ah the 100Ah configuration is doubled with separate battery connection wires to controller 24V two ba...

Страница 4: ... Set the proper voltage on the AC input of the controller by removing the metal tab and then switching the input voltage to 120VAC or 240VAC depending on your source voltage Be sure to replace the metal tab to ensure that somebody doesn t accidentally switch the voltage as this will damage the controller STEP 10 Connect the battery cables to the controller then to the bat tery Be sure to observe p...

Страница 5: ...re in the seal area to increase its diameter and make a better seal The enclosure needs some small amount of venting so be sure NOT to seal all holes and feedthrus with silicon STEP 15 Make sure lid gasket is clean and free from any particles then carefully close the cover making sure that wires are clear of the seam and hinge area Use the special key to close the two cover locks TECH CORNER Addit...

Страница 6: ...temperatures If the batteries get discharged less than 10V you will need to recondition them by charging them with a good 10A auto motive battery charger Don t charge for more than 24hrs else you SPECIFICATIONS Subject to change without notice UPS ST12 UPS ST24 UPS ST48 Load Voltage 12V 0 5 24V 0 5 48V 0 5 Max Load 10A 120W 5A 120W 2 5A 120W Min Load 1A 1A 1A Capacity 1 battery 51Ah 600VA 2 batter...

Страница 7: ...rated connection cabling Solar panels have a 25 year output warranty Pole mounts and panels are designed for wind loads to 90MPH Note Solar panel kits are only available for 12V and 24V Battery Sys tems Compatible Wind Turbine Solar Kits 6 Hours Peak Sun 3 Hours Peak Sun TPSK12 80W 20W continuous 10W continuous TPSKxx 160W 40W continuous 20W continuous TPSKxx 320W 80W continuous 40W continuous TPS...

Страница 8: ...s material and workmanship defects This warranty does not cover the following Parts requiring replacement due to improper installation misuse poor site conditions faulty power etc Lightning or weather damage Physical damage to the external internal parts Products that have been opened altered or defaced Water damage for units that were not mounted according to user manual Usage other than in accor...

Отзывы: