Valve Plunger Assembly shown in Figure 2, move freely
to the left.

NOTE

When removing the Handhole Cover, first loosen all of the
Cover Bolts, and then remove all but two of the Cover Bolts.
Remove the last two Cover Bolts while securely holding the
Handhole Cover, so as to prevent dropping the Handhole
Cover which could result in personal injury.

8. With your left hand holding the Clapper Assembly and

your right hand pushing the Latch Pawl (Fig. 3), unlatch
the Clapper Assembly and carefully lower the Clapper
Assembly into the set position with the Clapper Arm (7 -
Fig. 2) under the Retaining Lever (21 - Fig. 2).

NOTE

Use care when lowering the Clapper Assembly to avoid
pinching your fingers, and make certain that the Clapper
Assembly is fully seated (i.e., not latched in either the first or
second positions shown in Figure 3).

9. Reach into the handhole opening and while holding onto

the Differential Valve Plunger (31 - Fig. 2), rotate the Dif-
ferential Valve Plunger and pull it towards the Retaining
Lever. As the Differential Valve Disc (36 - Fig. 2) seats
against the Differential Valve Seat (30 - Fig. 2) within the
Differential Valve Housing, some resistance to rotation
should be felt to indicate adequate seating.

10. Inspect the Handhole Cover Gasket for breaks and re-

place the Handhole Cover and Handhole Cover Gasket.
Tighten the Handhole Cover Bolts with a cross-draw se-
quence.

11. Replace all damaged or operated sprinklers. Replace-

ment sprinklers must be of the same type and tempera-
ture rating as those which operated.

NOTE

In order to prevent the possibility of a subsequent operation,
any solder type sprinklers which were possibly exposed to a

temperature greater than their maximum rated ambient must
also be replaced.

12. Service the air dryer, if applicable, in accordance with

the manufacturer’s instructions.

13. Open (energize) the Solenoid Valve (Fig. 7) by manually

operating the releasing panel.

14. Open the Differential Chamber Supply Control Valve

(Fig. 7) and allow water to discharge from the Dry Pilot
Actuator.

15. Close the operating lever of the Manual Control Station

(Fig. 7). Close the hinged cover and insert a new break
rod (#922891008) in the small hole through the top of
the enclosing box.

16. Return the Solenoid Valve to its normally closed position

by resetting the releasing panel, and allow time for full
pressure to build up in the Differential Chamber.
Observe the Vent Fitting (23 - Fig. 6) connected to the
Neutral Chamber for leaks. If there are leaks, the Differ-
ential Valve Assembly may not be properly seated and
the Differential Valve Assembly must be inspected. De-
termine/correct the cause of the leakage problem by re-
ferring to the Maintenance and Service section.

17. If resetting after a test, fully open the System Shut-Off

Valve (Fig. 1).

18. Open the Air Supply Control Valve and pressurize the

sprinkler system in accordance with Figure 5.

19. Inspect the drain connections from the Dry Pilot Actua-

tor and Manual Control Station for leaks. Leaks, if any,
must be corrected before the system is restored to serv-
ice.

20. Reset the S430 Accelerator (Fig. 8) using the following

Steps a through l, if the system is so equipped; other-
wise, proceed to Step 21.

a. Close the Accelerator Control Valve.

STAR SPRINKLER INC.

2-4.1.10

Page 9

FIGURE 10

3 INCH (DN80) MODEL A PREACTION VALVE AND TRIM INSTALLATION DIMENSIONS

ELECTRIC/PNEUMATIC DOUBLE INTERLOCK PREACTION SYSTEM

10-1/4"

(260.4 mm)

6-1/8"

(155.6 mm)

17-7/8"

(454.0 mm)

16-3/4"

(425.5 mm)

26-3/8"

(669.9 mm)

12-1/8"

(308.0 mm)

MAIN

CONTROL

VALVE

DIFFERENTIAL

CHAMBER SUPPLY

(FIELD FABRICATED)

14-3/4" (374.7 mm)

WHEN MODEL S430

ACCELERATOR

IS USED

ADD

OBSOLETE

Содержание STAR Model A

Страница 1: ...alve in a se ries configuration is utilized The double seat design of the Model A Preaction Valve isolates the system air pres sure which holds the Dry Pilot Actuator closed The Sole noid Valve remains closed until it is electrically energized by a releasing panel that is operated by either an electric fire detection device or electric manual pull station As an option for water supplies of 35 psi ...

Страница 2: ...ainer 1 5596 21 Retaining Lever 1 5621 22 Water Seat Disc 1 5634 23 Disc Retaining Ring 1 5637 24 Air Seat Disc 1 5827 25 Differential Valve Housing 1 5573 26 Differential Valve Housing Gasket 2 5577 27 Differential Valve Housing Cover 1 5574 28 Differential Valve Housing Cover Bolt 5 8 11UNC x 3 1 2 4 1020 27 29 Roll Pin 2 1893 02 30 Differential Valve Seat 1 NR 31 Differential Valve Plunger 1 55...

Страница 3: ...MBLY CLAPPER 04 07 05 ASSEMBLY RESTRICTOR LOCATED VALVE ON BACK OF NEUTRAL CHAMBER VALVE PLUNGER ASSEMBLY DIFFERENTIAL CAUTION LATCH POSITION SECOND LATCH CLAPPER LATCH FIRST POSITION REFER TO SETTING PROCEDURE STEP 8 01 08 PUSH HERE TO UNLATCH CLAPPER 02 LEVER RETAINING ENGAGED CLAPPER ARM 03 WATER SUPPLY PRESSURE DIFFERENTIAL CHAMBER SUPPLY DIFFERENTIAL CHAMBER VENT PORT IDENTIFICATION MAIN DRAI...

Страница 4: ... pressure in the Differential Chamber is reduced to approximately one fifth of the water supply pressure Opening of both the Solenoid Valve and Dry Pilot Actua tor or operating the Manual Control Station will release water from the Model A Preaction Valve Differential Cham ber faster than it can be replenished through the 3 32 inch 2 4 mm diameter orifice of the Restrictor Assembly A rapid pressur...

Страница 5: ... test or performing a system trip test Installation configuration and clearance dimensions are given in Figure 10 The flanged inlet and outlet connec tions are faced and drilled per ANSI Standard B16 1 un less otherwise specified when ordered In order to readily perform the System Inspection Proce dure described in the Maintenance and Service section it is recommended that a System Shut Off Valve ...

Страница 6: ...lve S410 1 1133 1 13 1 2 Ball Valve 1 923001002 NO DESCRIPTION QTY PART 14 1 2 Globe Valve 1 460471004 15 1 2 Swing Check Valve 1 460491004 16 1 2 Y Strainer 1 523531005 17 1 2 Spring Loaded Check Valve 1 923221002 18 3 4 Swing Check Valve with 3 32 Orifice 1 524031005 19 1 1 2 Angle Valve 1 460481008 20 Drip Funnel Support Plug 1 922111005 21 Drip Funnel Support 1 922111003 22 Drip Funnel 1 92343...

Страница 7: ...ressure setting After verifying the desired pres sure setting tighten the jam nut 9 Suitable provision must be made for disposal of drain water Drainage water must be directed such that it will not cause damage or result in dangerous conditions 10 All conduit and electrical connections are to be made in accordance with the requirements of the Authority Hav ing Jurisdiction and or the National Elec...

Страница 8: ...drain close the Inspector s Test Connection all auxiliary drains in the system piping and the Low Body Drain Valve Leave the Main Drain Valve open 6 Clean out the Strainer 16 Fig 6 in the connection to the Model A Preaction Differential Chamber Reassem ble the Strainer after cleaning 7 Remove the Handhole Cover 4 Fig 2 and then care fully clean the Water Seat Disc Air Seat Disc Seat Ring and Clapp...

Страница 9: ... also be replaced 12 Service the air dryer if applicable in accordance with the manufacturer s instructions 13 Open energize the Solenoid Valve Fig 7 by manually operating the releasing panel 14 Open the Differential Chamber Supply Control Valve Fig 7 and allow water to discharge from the Dry Pilot Actuator 15 Close the operating lever of the Manual Control Station Fig 7 Close the hinged cover and...

Страница 10: ...l station alarms The Model A Preaction Valve is now set for service MAINTENANCE AND SERVICE The Model A Preaction Valve requires regularly sched uled maintenance and service In addition it is recom mended that the proper operation of the system and con dition of the system in which it is utilized be periodically verified in accordance with the following described inspec tion procedure Any impairme...

Страница 11: ...edure section SERVICE RECOMMENDATIONS Drop In Water Supply Pressure Below Normal Range NOTE If the water supply pressure is significantly reduced be low the normally expected static pressure range as could occur in the case of a water main break or repair and there is a subsequent drop in the differential cham ber water pressure below its normal range due for exam ple to a leak in a piping connect...

Страница 12: ...ntial Valve Plunger Assembly is accomplished by varying the thread engagement be tween the Plunger Nose and the Plunger Start with an overall assembly length of 4 7 8 inches and then insert the Differential Valve Assembly into the Differential Valve Seat With the Clapper Assembly seated and while pulling the Retaining Lever from left to right push the Differential Valve Plunger Assembly completely...

Отзывы: