The Programming Sections in this document are accessed via panel Section for Ethernet/GPRS Programming.
Enter:
[*][8][installer code][851][###]
, Where ### is the 3 digit Section number referenced in this document.
The Programming Worksheets at the end of this document can be used to record the new values when pro-
gramming changes have been made from the default values. Default values are provided for each Section.
Programming Sections can not be modified from the keypad. Installers may review/record programming
Options at the keypad.
NOTE:
Ethernet/GPRS Programming Sections accessed through the panel are for display purposes
only. Configuration changes must be done remotely
. Specified panel Sections must be configured for
proper operation of the Communicator and the panel.
System Options
[001] Ethernet IP Address
Default (000.000.000.000)
Enter the IP address of the Communicator. Ensure that the IP address is unique to your Communicator on the local
network. Format is 4 fields, each field is a 3 digit decimal number. Valid range: 000-255. If an IP address is pro-
grammed in this Section, the unit will operate with Static IP (DHCP disabled). Sections [002] and [003] must also be
programmed when using Static IP addresses.
NOTE: Default for this Section is Dynamic Host Configuration Protocol (DHCP) enabled. When enabled,
the DHCP Server will set values for: IP Address [001], Subnet Mask [002], and Gateway [003]. Program-
ming an IP address in this Section will disable DHCP (Static IP).
[002] Ethernet IP Subnet Mask
Default (255.255.255.000)
Enter the Ethernet IP Subnet Mask of the dual Communicator. Format is 4 fields, each field is a 3 digit decimal
number. Valid range: 000-255.
NOTE: If DHCP is enabled, the DHCP Server will assign the subnet mask for this Section and the pro-
grammed value will be ignored.
[003] Ethernet Gateway IP Address
Default (000.000.000.000)
Enter the Ethernet Gateway IP address of the dual Communicator. The gateway IP address is required when a
router is used on the local network to reach the destination IP address specified in Section [001]. Format is 4 fields,
each field is a 3 digit decimal number. Valid range: 000-255.
NOTE: If DHCP is enabled, the DHCP Server will assign the Gateway IP address for this Section and the
programmed value will be ignored.
[004] Receiver Supervision Interval
Default (0087/135)
When receiver supervision is enabled (ON) in Section [005] Toggle Option [3], the unit sends heartbeats to Ether-
net Receiver 1 or GPRS Receiver 1 to test the communication path. Use this Section to set the interval time (in sec-
onds) when heartbeats will be sent. Valid range 000
A
-FFFF seconds.
If the programmed value is less than (000A/
10
) seconds, supervision is disabled.
•
Receiver Window:
This is the supervision timeout that needs to be configured at the central station receiver.
•
Recommended Values:
This is the recommended heartbeat interval that should be programmed into the
Communicator module.
• For ULC passive systems (not using heartbeat supervision), the daily test transmission must be enabled over
each available communication channel Section [125] and [225]. When programming with Connect24, the
recommended intervals will be programmed automatically when the required window is selected.
[005] System Toggle Options
[1] Ethernet Receiver 1 Supervised
Default (OFF) TL260-RS/TL260GS-RS only.
ON
: Ethernet Receiver 1 will be supervised and heartbeats will be sent to Ethernet Receiver 1 based on the
supervision interval programmed in Section [004].
OFF
: Ethernet Receiver 1 will not be supervised. When disabled, heartbeat 1 is sent to the Ethernet receiver
once every hour, regardless of supervision type (heartbeat 1 or 2). The heartbeat is resent every 5 seconds until
ACK. If no event or heartbeat ACK is received after (Receiver Supervision In 75 seconds), Supervisory
trouble is indicated (8 flashes).
NOTE: Ethernet Receiver 2 can not be supervised.
[2] GPRS Receiver 1 Supervised
Default (OFF)
ON
: GPRS Receiver 1 will be supervised and heartbeats will be sent to GPRS Receiver 1 based on the super-
vision interval programmed in Section [004]. If ACK to heartbeat is not received, it is retransmitted every 5 sec-
onds. Failure to ACK 2 consecutive heartbeats will reset the radio.
ETHERNET/GPRS PROGRAMMING SECTIONS
Table 7: Supervision Intervals for UL/ULC
Jurisdiction
Receiver Window
(Timeout)
Recommended Supervision
Interval
UL Commercial Burglary
200 seconds
(0087/135) seconds
UL Residential Fire
30 days
Panel Test Transmission
UL Residential Burglary
30 days
Panel Test Transmission
ULC Commercial Burglary Active
180 seconds
(005A/90) seconds
ULC Commercial Burglary Passive
24 hours
Panel Test Transmission
ULC Commercial Fire Active
180 seconds
(0073/115) seconds
ULC Commercial Fire Passive
24 hours
Panel Test Transmission