Step 5.
Install the insulation.

Thermal insulation must be used. It protects the Frostex heat-
ing cable from damage and helps keep the pipes from freezing.
Before you insulate, be sure the Frostex heating cable is
undamaged—no nicks or cuts—and the braid is intact.
Replace the heating cable if necessary. 

5A.

Cover the system with the insulation.

Cover the pipe, heating cable, connections, valves, and spigots
with clean, dry, waterproof, fire-retardant thermal insulation,
such as closed-cell foam insulation, as shown in Figure 7. The
insulation must be at least as thick as selected in Table 1 or 2.

Secure the 9800 FlexFit plug to the insulation with tape or
plastic cable ties, being careful not to cover the light or test
buttons.

Figure 7. Thermal insulation.

• Do not leave the heating cable exposed, except for the

short distance from the pipe to the power connection.

• Fully insulate and weatherproof all exposed piping. Put

additional insulation on areas that cannot be heat traced. 

5B.

Waterproof the insulation.

Make sure the thermal insulation is waterproof and stays dry.
Install a watertight sleeve and a solid cover or a barrier such as
polyethylene sheeting around the insulation wherever there is
any chance that the insulation might get wet.

5C.

Install the warning label.

Install the orange warning labels on the insulation with one
near the electrical outlet, as shown in Figure 7.

Additional labels and installation tape are available from Tyco
Thermal Controls in the Frostex 9610 kit.

Step 6.
Start up the system.

6A.

Plug in the heating cable.

After installing the heating cable and insulation, remove the
clear label that covers the test and reset buttons. Then, plug the
9800 FlexFit plug into a grounded and properly installed outlet.

• If the Frostex heating cable length is longer than 40 feet

and the air temperature is lower than 30°F, run water
through the pipe before plugging in the unit. This will
warm up the pipe and help avoid blowing the nonreplace-
able fuse in the 9800 FlexFit plug.

• The signal light will go on indicating that the ground-fault

protection device and the fuse are working properly.
However, the light does not confirm that the heating cable
is properly connected. See Step 7, “Test the System.”

6B.

Test the plug.

• Press the white test button. The red reset button should

pop out from the surface of the plug and the signal light
should go out.

• When the red reset button pops out, push it in to restore

power and proceed to Step 7.

If the red reset button fails to pop out, skip to
“Troubleshooting.”

If the red reset button pops out immediately but cannot
be reset, skip to “Troubleshooting.”

If the signal light does not light, skip to “Troubleshooting.”

Step 7. 
Test the system.

Test the system using one of the two following procedures.

7A.

Test the water temperature.

After plugging in the system, wait about an hour. Turn on a
water tap on the Frostex-protected pipe and test the tempera-
ture of the water. It should feel warm almost immediately
because the water heated by the Frostex heating cable will be
briefly running through the pipe.

If the water is warm, you have completed the installation.
If the water is not warm, skip to “Troubleshooting.”

7B.

Test the heating cable’s resistance.

It is possible to test the resistance of Frostex heating cable
using a multimeter. Follow these steps:

• Be sure the 9800 FlexFit plug is unplugged.
• Push in the red reset button on the plug.
• Connect the two lead wires on the meter to the two flat

prongs on the plug. The meter reading should be between
2 and 20,000 ohms. 

If your reading is within this range, you have completed
the installation.

If your reading is not within this range, repeat Step 3,
“Install the 9800 FlexFit plug” and retest.

If your reading is still not within this range or you 
have questions, call Tyco thermal controls for techni-
cal support at (800) 545-6258.

Warning

labels

7

ENGLISH

Содержание Frostex 9800

Страница 1: ...9800 FlexFit Plug Kit Directives d installation et Guide de l Utilisateur du Syst me Frostex de Protection Anti gel des Tuyaux Utilis avec le Kit Frostex 9800 FlexFit Keep pipes from freezing Protecti...

Страница 2: ...D pannage 16 Garantie limit e 17 Avant de d buter Assurez vous que votre kit 9800 FlexFit contient tout ce qui suit 1 Fiche 9800 FlexFit 1 Obturateur pousser 2 tiquettes oranges d avertissement en ang...

Страница 3: ...quat Employez uniquement les versions tress es des c bles chauffants Frostex Les versions ant rieures des c bles chauffants Frostex sans tresses ne sont pas compatibles 2 Utilisez la fiche et l obtur...

Страница 4: ...nt safety warnings and maintenance information If you have any difficulty installing the system please contact Tyco Thermal Controls for information at 800 545 6258 or call a professional service pers...

Страница 5: ...rostex heating cable installed along the entire length of the pipe Table 2 The total length of heating cable equals 32 ft 10 m 2 runs x 16 ft 5 m of pipe 1 ft 0 3 m for one ball valve 1 ft 0 3 m for o...

Страница 6: ...able 2C Remove the plastic wrap Cut and remove the clear plastic wrap Do not cut into the blue jacket 2E Secure the braid Slide the braid up against the end seal and wrap it securely with a 4 10 cm st...

Страница 7: ...The clear plastic wrap does not need to be removed 3C Complete the connection Screw down the cable guide alternating between the two screws until the cable guide is flush with the indicator posts and...

Страница 8: ...cable in the 4 o clock and 8 o clock positions as shown in Figure 4 When three runs are required install the heating cable as shown in Figure 5 Figure 4 Double runs Figure 5 Triple runs 4C Tape the he...

Страница 9: ...lower than 30 F run water through the pipe before plugging in the unit This will warm up the pipe and help avoid blowing the nonreplace able fuse in the 9800 FlexFit plug The signal light will go on i...

Страница 10: ...e replaced Problem The signal light does not light up What to do Check to be sure the outlet has power If you are not certain how to do this call a professional service person If the outlet has no pow...

Страница 11: ...goods to Tyco Thermal Controls postage prepaid at 300 Constitution Drive Menlo Park California 94025 1164 USA and c Tyco Thermal Controls examination of such goods estab lishes to Tyco Thermal Control...

Отзывы: