Pipe Thread Connection

1/2 inch NPT

Discharge Coefficient

K = 5.6 GPM/psi

1/2

(80,6 LPM/bar

1/2

)

Temperature Ratings

Refer to Table A

Finishes

Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated

Physical Characteristics

Frame

. . . . . . . . . . . . Bronze

Button

. . . . . . . . . . . . Bronze

Sealing Assembly . . . . . . . . . .

. . . . . . Beryllium Nickel w/Teflon†

Bulb

. . . . . . . Glass (3 mm dia.)

Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Copper

† Registered trademark of DuPont

Operation

The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass  bulb,  allowing  the  sprinkler  to
activate and water to flow.

Design
Criteria

The Series EC-5 Extended Coverage
Horizontal Sidewall Sprinklers must be
installed and utilized in Light Hazard
Occupancies, under smooth level ceil-
ings as outlined in the applicable in-
stallation standard recognized by the
Approval Agency (e.g., UL recognizes
NFPA 13, and FM recognizes the FM
Loss Prevention Data Sheets). Only
the Style 50 Recessed Escutcheon, as
applicable, is to be used for recessed
installations.

Installation

The Series EC-5 Sprinklers must be
installed in accordance with the follow-
ing instructions:

NOTES

Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).

A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque

Page 2 of 6

TFP298

FIGURE 1

SERIES EC-5 (TY3302) EXTENDED COVERAGE

HORIZONTAL SIDEWALL SPRINKLERS

WRENCH

FLATS

1/2"

NPT

**

6

*

1

2

3

4

5

-

2

Button

Temperature

on Deflector.

Deflector

Compression Screw

Bulb

Sealing Assembly

-

6

*

-

4
5 -

3 -

*

Components:

Frame

1 -

Pipe thread
connections per
ISO 7/1 can be

**

provided on

(33,3 mm)

(52,4 mm)

2-1/16"

1-5/16"

(7,9 mm)

5/16"

SURFACE

ESCUTCHEON

PLATE SEATING

7/16"

MAKE-IN

NOMINAL

(11,1 mm)

OF SPRINKLER

WATERWAY

CENTERLINE

(38,1 mm)

1-1/2"

DEFLECTOR

HAT

special request.

rating is indicated

7/16"

(11,1 mm)

FIGURE 2

SERIES EC-5 RECESSED EXTENDED COVERAGE HORIZONTAL

SIDEWALL SPRINKLER ASSEMBLY WITH TWO-PIECE

3/8 INCH TOTAL ADJUSTMENT STYLE 50 RECESSED ESCUTCHEON

MOUNTING

7/8" (22,2 mm)

1-1/8" (28,6 mm)

PLATE

CLOSURE

SURFACE

MOUNTING

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

3/16" (4,8 mm)

7/16" (11,1 mm)

(2,4 mm)

3/32"

9/16±1/8"

FACE OF

FITTING

SPRINKLER

(14,2±3,2 mm)

2-7/8" DIA.

Содержание EC-5 Series

Страница 1: ...entative of all possible cor rosive atmospheres Consequently it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corro sive environment The effects of ambi ent temperature concentration of chemicals and gas chemical velocity should be considered as a minimum along with the corrosive nature of the chemical to which the sprinklers will be ...

Страница 2: ... be installed in accordance with the follow ing instructions NOTES Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb With the sprinkler held horizontally a small air bubble should be present The diameter of the air bubble is approximately 1 16 inch 1 6 mm A leak tight 1 2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft ...

Страница 3: ...on system main control valve for maintenance work on the fire protection system that it controls permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified Absence of an escutcheon which is used to cover a clearance hole may delay the time to sprinkler operation in a fire situation S...

Страница 4: ... Deflector Sprinkler Minimum Rating Area 1 Flow 2 Pressure 2 To Ceiling Temperature Spacing 4 Ft x Ft m x m GPM LPM PSI BAR Distance 3 In mm Rating F Ft m Quick 16 x 16 4 9 x 4 9 26 98 21 6 1 48 4 to 18 100 to 450 135 155 8 2 4 Quick 16 x 16 4 9 x 4 9 26 98 21 6 1 48 4 to 12 100 to 300 200 8 2 4 Quick 16 x 18 4 9 x 5 5 29 110 26 8 1 85 4 to 18 100 to 450 135 155 8 2 4 Quick 16 x 20 4 9 x 6 1 32 12...

Страница 5: ...NSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LABOR CHARGES RE GARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES AND IN NO EVENT SHALL TYCO FIRE PRODUCTS LI ABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT NESS FOR A P...

Страница 6: ...ecessed Escutcheon Chrome Plated PSN 56 711 9 010 White Color Coated PSN 56 711 4 010 White RAL9010 PSN 56 711 3 010 Brass Plated PSN 56 711 2 010 Eastern Hemisphere sales only Sprinkler Wrench Specify W Type 6 Sprinkler Wrench P N 56 000 6 387 Specify W Type 7 Recessed Sprinkler Wrench P N 56 850 4 001 Page 6 of 6 TFP298 TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale Pennsylvania 19446 51 XX...

Отзывы: