Inputs Activation Mode
The 3G3070-CF also has 4 inputs that can be used to trigger specific event transmissions. The events
associated with these inputs will be transmitted using Contact ID Communication Format. The default
settings for these inputs (as they should be correlated at the supervising station) are:
INPUT 1- AC LOSS
INPUT 3 - FIRE ALARM
INPUT 2 - FIRE SUPERVISORY
INPUT 4 - TROUBLE
These inputs are normally open type and will activate when a short condition is detected between the
terminal and the COM. Refer to the 3G3070-CF Wiring Diagram (Figure 2) at the back of this manual.
NOTE: When the 3G3070-CF is configured in Land Line Mode, these inputs should be restricted
to monitoring of trouble conditions.
NOTE: For UL listing, connections between alarm panel outputs and 3G3070-CF inputs shall be
run in mechanical protective conduit within 20ft and in the same room. To reduce interference with
the antenna, it is recommended that metal conduit is not connected to the knock-outs on the top
of the cabinet.
Activating the Outputs
The 3G3070-CF has four programmable outputs to activate in response to the associated events. Refer
to the 3G3070-CF Wiring Diagram (Figure 2) at the back of this manual.
The 3G3070-CF has 4 open collector outputs, switched to ground, capable of a maximum of 50mA.
Internal events on the 3G3070-CF can trigger the outputs to turn on an LED or activate an input on the
alarm control panel. The default settings are as follows:
OUTPUT 1 - Land Line T
OUTPUT 1 - Land Line T
OUTPUT 1 - Land Line T
OUTPUT 1 - Land Line T
OUTPUT 1 - Land Line Trrrrrouble:
ouble:
ouble:
ouble:
ouble: Output is normally high and will switch to ground when the telephone
line is down.
NOTE: Thi
s
o
u
tp
u
t i
s
not req
u
ired when the 3G3070-CF i
s
us
ed
as
a
s
t
a
nd
a
lone device.
OUTPUT 2 - W
OUTPUT 2 - W
OUTPUT 2 - W
OUTPUT 2 - W
OUTPUT 2 - Wir
ir
ir
ir
ireless Module or Network T
eless Module or Network T
eless Module or Network T
eless Module or Network T
eless Module or Network Trrrrrouble:
ouble:
ouble:
ouble:
ouble: Output is normally high and will switch to ground
when the 3G3070-CF cannot connect or communicate to the wireless network.
OUTPUT 3 - Activation:
OUTPUT 3 - Activation:
OUTPUT 3 - Activation:
OUTPUT 3 - Activation:
OUTPUT 3 - Activation: Output is normally high and will switch to ground during activation.
OUTPUT 4 - General Module T
OUTPUT 4 - General Module T
OUTPUT 4 - General Module T
OUTPUT 4 - General Module T
OUTPUT 4 - General Module Trrrrrouble:
ouble:
ouble:
ouble:
ouble: Output is normally low and will switch to high when any of the
previous troubles occur and/or a Failure to Communicate (FTC) trouble is detected.
NOTE: Once an output has been activated automatically, it will not restore its state until all the
causes of activation are cleared.
Contact ID Events Description
Event Codes
Input 1 Activation: ............................................................................................. E301 AC LOSS ZONE 991
Input 1 Restoral: ................................................................................................ R301 AC LOSS ZONE 991
Input 2 Activation: ................................................................................. E200 Fire Supervisory ZONE 992
Input 2 Restoral: .................................................................................... R200 Fire Supervisory ZONE 992
Input 3 Activation: ..................................................................................................... E110 FIRE ZONE 993
Input 3 Restoral: ........................................................................................................ R110 FIRE ZONE 993
Input 4 Activation: ................................................................................... E300 System Trouble ZONE 994
Input 4 Restoral: ...................................................................................... R300 System Trouble ZONE 994
PSTN Line Down: .............................................................................................. E351 TELCO 1 FAULT 000
PSTN Line Restoral: .......................................................................................... R351 TELCO 1 FAULT 000
Periodic Report: ........................................................................................ E603 Periodic RF Xmission 000
Periodic report with off-normal condition .. E608 Periodic Test Xmission with System Trouble Present 000
GSM UNIT ACTIVATION: ....................................................................... R552 Radio Xmitter Disabled 000
GSM INTERNAL BUFFER FULL: ...................................................... E624 EVENT LOG OVERFLOW 000
FTC RESTORAL: ......................................................................... R354 FAILURE TO COMMUNICATE 000
NOTE: The 3G3070-CF does not support local or remote programming. Upon activation through
Connect 24 the product will operate as described in the previous sections of this manual.