2.

INTRODUCTION

The AV Series of Loop Powered Addressable Sounder/
Sounder-Beacons are designed to be driven from an MX/ZX
controller via the addressable loop.

Tone, volume and flash rates are set in Consys.

3.

FEATURES

The sounder has four volume settings ‘High’ (90dB ±3), ‘Mid
High’ (80 ±3dB), ‘Mid Low’ (70 ±3dB)or ‘Low’ (60dB ±3).

The beacon has two flash rates ‘Slow Flash’ (1/2Hz) or ‘Fast
Flash’ (1Hz).

The AV Series have a built-in line isolator.

4.

CABLING

Cables are to be selected in accordance with Publication 17A-
02-D and the requirements of the current issue of BS5839.
Cabling should be connected as shown in Fig. 4 ensuring
correct polarity.

5.

WIRING NOTES

The following notes apply: 

a) All wiring must conform to the current edition

of IEE Wiring Regulations and BS 5839 Part 1.

b) All wiring must be free of earths.

6.

MOUNTING

6.1

INSTALLATION TO A FLAT SURFACE
USING TYPE ‘A’ MOUNTING FLANGE

THIS MOUNTING

FLANGE IS

SUPPLIED

WITH THE BASE

SOUNDER

BASE

CABLE
ENTRY

D

O

 N

O

T

 P

A

INT

 

DETECTOR

ELECTRICAL

BACKBOX

SOUNDER

BLANKING CAP

OPTION

(WHEN DETECTOR

NOT FITTED)

Fig. 2

Fitting to a Flat Surface

To install an AV base, proceed as follows:

a) Feed the addressable loop wiring through

the mounting flange cable entry.

c) Secure the mounting flange to a flat surface.

d) Feed the addressable loop wiring through

the AV base cable entry, then clip the
sounder base to the mounting flange.

e) Wire the AV base as shown in Fig. 7

ensuring correct polarity.

f) Fit the locking device (supplied) to the

base, pressing it in until it is fully
seated. See Fig. 4.

g) Fit the address flag to the detector. Fit the

detector to the sounder base, (the address
flag will be transferred to the sounder base).

INSTALLATION TO A FLAT SURFACE
USING DAB3-4 MOUNTING FLANGE

To install an AV base, proceed as follows:

a) Remove the required number of conduit

knockouts.

b) Fit the conduit, feed the cables through the

conduit and the cable entry hole of the
mounting flange.

c) Fit the mounting flange to the conduit and

secure with suitable screws.

d) Clip the AV base to the mounting flange.

e) Wire the AV base as shown in Fig. 7

ensuring correct polarity.

f) Fit the locking device (supplied) to the

base, pressing it in until it is fully
seated. See Fig. 4.

g) Fit the address flag to the detector. Fit the

detector to the sounder base, (the address
flag will be transferred to the sounder base).

THE DAB3-4

MOUNTING

FLANGE

MUST BE

ORDERED

SEPARATELY

SOUNDER BEACON

BASE

CABLE
ENTRY

D

O

 N

O

T

 P

A

I

NT 

DETECTOR

SOUNDER

BLANKING CAP

OPTION

(WHEN DETECTOR

NOT FITTED)

Fig. 3

Fitting Using Conduit

Содержание 800 Series

Страница 1: ...r only 160g Sounder Beacon 190g Mounting Requirements Surface mount The flat surface mounting flange is supplied with the base The DAB3 4 mounting flange must be ordered separately The mounting flanges have to four drill positions for mounting holes at 50mm 60mm 70mm and 80mm The sounder sounder beacon body clips onto the mounting flange Electrical Characteristics Addressable Loop Voltage 20 40Vdc...

Страница 2: ...sable loop wiring through the mounting flange cable entry c Secure the mounting flange to a flat surface d Feed the addressable loop wiring through the AV base cable entry then clip the sounder base to the mounting flange e Wire the AV base as shown in Fig 7 ensuring correct polarity f Fit the locking device supplied to the base pressing it in until it is fully seated See Fig 4 g Fit the address f...

Страница 3: ...e missing C Tick mark on the product identification label on the underside of the tool see Fig 5 Fig 4 Fitting Locking Device LOCKING DEVICE FOR MX ADDRESSABLE DEVICES USES TYCO MX DIGITAL PROTOCOL 801AP 516 800 918 MX SERVICE TOOL Tyco Safety Products N1156 DUNHAMS LANE LETCHWORTH SG6 1BE UK S N FF FF FF FF Fig 5 C TICK MARK The AV Sounder Beacons use 2 consecutive addresses on the MX addressable...

Страница 4: ...A 03 AV 2 11 08 PAGE 4 of 4 JM pl 20th November 2008 MX CONTROLLER L L1 L2 R L L1 L2 R L L1 L2 R L L1 L2 R L L1 L2 LPSB3000 LPAV3000 BASE 5BI BASE 5B BASE 5B BASE 5B BASE M M M M M Fig 7 AV Simplified Wiring Diagram ...

Отзывы: