Fig. 1

801AP MX Service Tool 

801AP MX SERVICE TOOL

USER INSTRUCTIONS

1.

INTRODUCTION

The 801AP MX Service Tool is used to program the loop address
into MX addressable devices. (A Quick Functional Reference
Table is detailed on page 10). 

The 801AP displays information and performs tests on devices.
It has a 32 character backlit LCD alphanumeric display, arranged
in 2 rows of 16 characters and four ‘softkeys’, F1, F2, F3 and F4.
(The display format is shown in Fig. 5).

Power for the 801AP is derived from 4 AA size nickel metal
hydride rechargeable batteries. It may be run from an unregulated
+12V dc input ie, car cigarette lighter connection or 110/230V ac
mains adaptor, both of which will recharge the batteries as well.
The 801AP consists of the following: 

MX Service Tool

Service Tool to ancillary connector lead

110 or 230V ac adaptor plus lead

4 x rechargeable AA size Nickel Metal Hydride
batteries

The 801AP is designed to be used as a desktop unit, clipped to a
trouser belt or be carried with a shoulder strap. The 801AP has
four external connections:

DC IN +12V

From car cigarette lighter or 
110/230V ac mains adaptor 

AUX

Ancillary connection port 

PC

PC connection port for use with 
MX CONSYS (not yet available) 

µ

P

Internal micro-processor program 
download port for use with PMS -
Program Management Software. 

Detectors are programmed by placing the detector onto the
801AP and turning clockwise until fully engaged.

Ancillaries are programmed via the AUX port on the 801AP.
The ancillary programming cable consists of an RJ11
connector at one end and a custom moulded connector at the
other end. 

2.

TECHNICAL SPECIFICATION

2.1

MECHANICAL

Dimensions

HWD:

48 x 200 x 112mm

Weight

801AP Service Tool:

 0.36kg

801AP Service Tool + batteries:

 0.5kg

Materials

Top: 

FR ABS Dark Blue

Bottom: 

FR ABS Dark Blue

Содержание 516.800.918

Страница 1: ...ll recharge the batteries as well The 801AP consists of the following MX Service Tool Service Tool to ancillary connector lead 110 or 230V ac adaptor plus lead 4 x rechargeable AA size Nickel Metal Hy...

Страница 2: ...on the base of the 801AP using a cross point screwdriver holding the battery compartment cover whilst removing it b Insert the batteries ensuring correct polarity as shown inside the battery compartm...

Страница 3: ...e remaining CAUTION ONCE THE HOURS LEFT REACHES ZERO THE SERVICE TOOL BECOMES INOPERABLE AND MUST BE RETURNED TO THE BRANCH OFFICE When there is less than 50 hours the expiry time appears The screen d...

Страница 4: ...nu displays the option The top line position of text is always shown in relation to the F1 F4 buttons above In the Main Menu F1 scrolls left through the main menu options F2 or F3 select the menu opti...

Страница 5: ...gle Option If Write is selected then the following message will appear for 2 seconds This is followed by Having programmed an address the Service Tool moves to the next sequential address This may be...

Страница 6: ...is available on the following types of detectors MX Ionisation MX Optical Heat Optical sensing element only MX CO Heat CO sensing element only Note Self test is NOT available for the heat sensing chan...

Страница 7: ...rients eg CP840Ex Callpoint the LED can not be made to illuminate unless the device is powered from the addressable loop Observe the warning see DIGITAL OUTPUTS when connecting the Service Tool to a d...

Страница 8: ...urns itself off The preset time period may be increased or decreased firstly in 1 minute steps then in 5 minute steps up to 60 minutes maximum Use Dn and Up to decrease or increase the timer period Ch...

Страница 9: ...ion is not normally used If the buttons or display are not responding correctly the Service Tool may be reset This is done by pushing a small jewellers type screwdriver into the pinhole on the bottom...

Страница 10: ...e identification value LED Mode Blnk flashes each time the device is polled Off switches OFF the blinking option Tst tests of the LED Digital Inputs Displays the status of the digital inputs in addres...

Отзывы: