3
Safety Information
IMPORTANT:
The equipment is fixed, wall-mounted and shall be installed in the position specified in these
instructions (see Figure 1: Parts). The equipment enclosure must be fully assembled and closed, with all the
necessary screws/tabs and secured to a wall before operation. Internal wiring must be routed in a manner that
prevents:
- Excessive strain on wire and on terminal connections
- Loosening of terminal; connections
- Damage of conductor insulation
Never install this equipment during a lightning storm!
Instruct the end-user to:
- Not attempt to service this product. Opening or removing covers may expose the user to dangerous voltages
or other risks. Any servicing shall be referred to trained service persons only.
- Use authorized accessories only with this equipment.
Do not dispose of the battery in fire or water. Disposing of the battery in a fire will cause rupture and explo-
sion.
Do not dispose of the waste battery as unsorted municipal waste. Consult your local regulations and /or laws
regarding recycling with regard to this lead-acid battery. Doing so will help protect the environment. Some of
the materials that are found within the battery could become toxic if not disposed of properly and may affect
the environment.
This equipment, 3G4010/LE4010, is fixed and shall be installed by Service Persons only (Service Person is
defined as a person having the appropriate technical training and experience necessary to be aware of hazards
to which that person may be exposed in performing a task, and of measures available to minimize the risks to
that person or other persons). It shall be installed and used within an environment that provides the pollution
degree max 2, over voltages category II, in non-hazardous, indoor locations only. This manual shall be used
with the Installation Manual of the relevant alarm control panel. All instructions specified within that manual
must be observed.
The performance of the 3G4010/LE4010 depends greatly on cellular network coverage. Therefore, it should
not be mounted without first performing placement tests to determine the best location for reception (minimum
of one green LED ON). Optional antenna kits – LTE-8ANT, LTE-15ANT, LTE-25ANT, LTE-50ANT
(8ft/2.4m, 15ft/4.6m, 25ft/7.6m or 50ft/15.2m) – are available.
Approvals Information
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the require-
ments in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming
features or options must be limited to the specific values or not used at all as indicated below.
Program Feature or Option
Permitted
in UL 864
(Y/N?)
Possible Settings
Settings Permitted in UL 864
Supervision
Yes
5 minutes /60 minutes
5 minutes (see note below)
Inputs/Outputs
Yes
Fire/Burg signals
Fire related signals only
SMS Remote Control
No
Enable/Disable
Disable
Note:
This product has been tested in accordance with UL 864 9th edition. According to this edition of the
standard, the supervision window for reporting single-technology communicator trouble shall be set to five
minutes. However, the product can be installed in accordance with the requirements of NFPA72 2013 edition,
which allows for a 60-minute supervision window.