TFP443

Page 3 of 6

Technical  

Data

Approvals

UL and C-UL Listed
The TYCO RAPID RESPONSE Series 

LFII Residential Flat-Plate Concealed 

Pendent Sprinklers are only listed with 

the Series LFII Concealed Cover Plates 

having a factory-applied finish.
These Cover Plates and their part num-

bers can be found in the Ordering Pro-

cedure section at the end of this data 

sheet.
For details on approvals, refer to the De-

sign Criteria section.

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K = 4.9 GPM/psi

1/2

 (70,6 LPM/bar

1/2

)

Temperature Rating

Sprinkler: 160°F (71°C) 

Cover Plate: 139°F (59°C)

Vertical Adjustment

1/2 inch (12,7 mm)

Finishes

Refer to the Ordering Procedure section.

Physical Characteristics

Cover Plate/Retainer Assembly:
 

Cover Plate . . . . . . . . . . . . . . . . . . . . . Copper

 

Ejection Spring . . . . . . . . . . . . Stainless Steel

 Retainer 

. . . . . . . . . . . . . . . . . . . . . . . . Brass

Sprinkler/Support Cup Assembly:
 Body . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass 
 Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze 
 Saddle. . . . . . . . . . . . . . . . . . . . . . . . . . Brass 
 

Sealing Assembly. . . . . . . . . . . . . .  Beryllium  

Nickel w/ TEFLON

 

Soldered Link Halves . . . . . . . . . . . . . . Nickel

 Lever . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
 

Compression Screw. . . . . . . . . . . . . . . Brass

 Deflector . . . . . . . . . . . . . . . . . . . . . . . Bronze
 

Guide Pin Housing . . . . . . . . . . . . . . . Bronze

 

Guide Pins  . . . . . . . . . . . . . . . . . . . . . Bronze

 

Support Cup   . . . . . . . . . . . . . . . . . . . . . Steel

Operation

When exposed to heat from a fire, the 

Cover Plate, which is normally soldered 

to the Retainer at three points, falls away 

to expose the Sprinkler/Support Cup As-

sembly. At this point, the Deflector, sup-

ported by the Guide Pins, drops down 

to its operated position.
The Solder Link Element of the Sprinkler/

Support Cup Assembly is comprised of 

two link halves that are soldered togeth-

er with a thin layer of solder. When the 

rated temperature is reached, the sol-

der melts and the two link halves sepa-

rate, allowing the sprinkler to activate 

and flow water.

Design Criteria

The TYCO RAPID RESPONSE Series 

LFII Residential Flat-Plate Concealed 

Pendent Sprinklers (TY2524) are UL 

and C-UL Listed for installation in ac-

cordance with this section:

Residential Sprinkler Design Guide

When conditions exist that are outside 

the scope of the provided criteria, re-

fer to the Residential Sprinkler Design 

Guide TFP490 for the manufacturer's 

recommendations that may be accept-

able to the authority having jurisdiction.

System Type

Per the UL Listing, wet pipe and dry pipe 

systems may be utilized. Per the C-UL 

Listing, only wet pipe systems may be 

utilized.

Refer to Technical Data Sheet TFP485 

about the use of Residential Sprinklers 

in residential dry pipe systems.

Ceiling Types

Smooth flat horizontal, or beamed, or 

sloped, in accordance with the 2013 

Edition of NFPA 13D, 13R or 13 as 

applicable.

Hydraulic Design 

(NFPA 13D and 13R)

For systems designed to NFPA 13D or 

NFPA 13R, the minimum required sprin-

kler flow rate are given in Tables A and 

B as a function of temperature rating 

and the maximum allowable coverage 

areas. The sprinkler flow rate is the mini-

mum required discharge from each of 

the total number of “design sprinklers” 

as specified in NFPA 13D or NFPA 13R. 

The number of “design sprinklers” spec-

ified in NFPA 13D and 13R for wet pipe 

systems is to be applied when designing 

dry pipe systems.

Hydraulic Design 

(NFPA 13)

For systems designed to NFPA 13, the 

number of design sprinklers is to be 

the four most hydraulically demanding 

sprinklers. The minimum required dis-

charge from each of the four sprinklers 

is to be the greater of the following:
•  The flow rates given in Tables A and 

B as a function of temperature rating 

and the maximum allowable cover-

age area

•  A minimum discharge of 0.1 gpm/ft

2

over the “design area” comprised of 

the four most hydraulically demand-

ing sprinklers for the actual coverage 

areas being protected by the four 

sprinklers

The number of “design sprinklers” 

specified in NFPA 13 for wet pipe sys-

tems is to be applied when designing 

dry pipe systems.

Dry Pipe System Water Delivery

When using the Series LFII Residential 

Flat-Plate Concealed Pendent Sprinklers 

(TY2524) in dry pipe sprinkler systems, 

the time for water delivery must not ex-

ceed 15 seconds for the most remote 

operating sprinkler.

Obstruction to Water Distribution

Sprinklers are to be located in accor-

dance with the obstruction rules of 

NFPA 13D, 13R, and 13 as applicable 

for residential sprinklers as well as with 

the obstruction criteria described within 

the Technical Data Sheet TFP490.

Operational Sensitivity

Install sprinklers relative to the ceiling 

mounting surface as shown in Figure 3.
The Series LFII Residential Flat-Plate 

Concealed Pendent Sprinklers must 

not be used in applications where the 

air pressure above the ceiling is greater 

than that below. Down drafts through 

the Support Cup can delay sprinkler op-

eration in a fire situation.

Sprinkler Spacing

The minimum spacing between sprin-

klers is 8 feet (2,4 m). The maximum 

spacing between sprinklers cannot ex-

ceed the length of the coverage area 

(Table A) being hydraulically calculated 

(e.g., a maximum of 12 feet for a 12 ft. x 

12 ft. coverage area or 20 feet for a 20 

ft. x 20 ft. coverage area.)