sprinkler waterway must be located 4-1/2 to 12-1/2
inches (114,3 to 317,5 mm) below the ceiling (Ref. Figure
2).

Only the Institutional Escutcheons shown in Figure 3 can
be utilized with the StarMax S102, and only a maximum
of three Spacers (#1752) can be utilized with Style B1 or
D Institutional Escutcheons when horizontal adjustment is
desired.

NOTES

The Sprinkler Body must not extend beyond the Institu-
tional Escutcheon (Ref. Figure 5). Otherwise the tamper
resistant design of the StarMax will be compromised.
Consequently, a maximum of three Spacers can only be
utilized with the Style B1 or D Institutional Escutcheons.

#1752 Spacers cannot to be utilized with the Style E
Institutional Escutcheons.

Integrity of the tamper resistant design of the Institutional
Escutcheon is dependent on the piping installation de-
sign. When installed properly, the Institutional Escutch-
eon is held fast to the mounting surface by the tightening
of the sprinkler assembly into the sprinkler fitting. In order
to accomplish a proper installation, the sprinkler fitting
must be properly located with respect to distance from
the face of the sprinkler fitting to the face of the mounting
surface (Ref. Figure 3); the sprinkler fitting being rigidly
secured and held immobile; and, the centerline of the
sprinkler fitting being perpendicular to the mounting sur-
face to assure that the escutcheon sits squarely against
the mounting surface around the entire perimeter of the
Institutional Escutcheon. Figure 2 illustrates a typical in-
stallation that can be utilized to help adjust the location
of the sprinkler fitting; to help assure immobility of the
sprinkler fitting; and, to help maintain perpendicularity of
the sprinkler fitting to the mounting surface.

STAR SPRINKLER

Page 2

1-5.3.11

FIGURE 1

5.6 K-FACTOR, STARMAX S102 QUICK RESPONSE

INSTITUTIONAL HORIZONTAL SIDEWALL SPRINKLER

(80.0 mm)

3.15"

SPRINKLER

FACE OF

3.18"

(80.8 mm)

7/16" (11.1 mm)

NOMINAL MAKE-IN

NPT

FITTING

1/2"

NOTCH (2)

OF SPRINKLER

WATERWAY

CENTERLINE

IN OPERATED

DEFLECTOR

POSITION

(12.7 mm)

1/2"

INSTALL SPRINKLER

WRENCHING

SPRINKLER

TOP AS SHOWN

WITH DEFLECTOR

HAT ORIENTED AT

FIGURE 2

TYPICAL INSTALLATION WITH #1780 RETAINING FLANGE AND #1781 CENTERING GROMMET

REDUCING COUPLING

1" x 1/2" M.I. CLASS 150

5/8" (15.9 mm)

w/ GROOVED

1" STEEL PIPE

WALL THICKNESS

RESULTS IN DEFLECTOR-

4" (101.6 mm) TO 12" (304.8 mm)

TO-CEILING DISTANCE OF

4-1/2" (114.3 mm) TO

12-1/2" (317.5 mm)

*

w/ ESCUTCHEON

MODEL S102

WATERWAY

OF SPRINKLER

CENTERLINE

FINISHED

CEILING

*

w/ SET SCREWS

RETAINING

FLANGE

GROMMET

#1781 CENTERING

#1780

2" SCH. 40

(LENGTH TO SUIT

STEEL PIPE SLEEVE

WALL THICKNESS)

OR 2" (50 mm) I.D.

CORED HOLE