sprinkler waterway must be located 4-1/2 to 12-1/2
inches (114,3 to 317,5 mm) below the ceiling (Ref. Figure
2).
Only the Institutional Escutcheons shown in Figure 3 can
be utilized with the StarMax S102, and only a maximum
of three Spacers (#1752) can be utilized with Style B1 or
D Institutional Escutcheons when horizontal adjustment is
desired.
NOTES
The Sprinkler Body must not extend beyond the Institu-
tional Escutcheon (Ref. Figure 5). Otherwise the tamper
resistant design of the StarMax will be compromised.
Consequently, a maximum of three Spacers can only be
utilized with the Style B1 or D Institutional Escutcheons.
#1752 Spacers cannot to be utilized with the Style E
Institutional Escutcheons.
Integrity of the tamper resistant design of the Institutional
Escutcheon is dependent on the piping installation de-
sign. When installed properly, the Institutional Escutch-
eon is held fast to the mounting surface by the tightening
of the sprinkler assembly into the sprinkler fitting. In order
to accomplish a proper installation, the sprinkler fitting
must be properly located with respect to distance from
the face of the sprinkler fitting to the face of the mounting
surface (Ref. Figure 3); the sprinkler fitting being rigidly
secured and held immobile; and, the centerline of the
sprinkler fitting being perpendicular to the mounting sur-
face to assure that the escutcheon sits squarely against
the mounting surface around the entire perimeter of the
Institutional Escutcheon. Figure 2 illustrates a typical in-
stallation that can be utilized to help adjust the location
of the sprinkler fitting; to help assure immobility of the
sprinkler fitting; and, to help maintain perpendicularity of
the sprinkler fitting to the mounting surface.
STAR SPRINKLER
Page 2
1-5.3.11
FIGURE 1
5.6 K-FACTOR, STARMAX S102 QUICK RESPONSE
INSTITUTIONAL HORIZONTAL SIDEWALL SPRINKLER
(80.0 mm)
3.15"
SPRINKLER
FACE OF
3.18"
(80.8 mm)
7/16" (11.1 mm)
NOMINAL MAKE-IN
NPT
FITTING
1/2"
NOTCH (2)
OF SPRINKLER
WATERWAY
CENTERLINE
IN OPERATED
DEFLECTOR
POSITION
(12.7 mm)
1/2"
INSTALL SPRINKLER
WRENCHING
SPRINKLER
TOP AS SHOWN
WITH DEFLECTOR
HAT ORIENTED AT
FIGURE 2
TYPICAL INSTALLATION WITH #1780 RETAINING FLANGE AND #1781 CENTERING GROMMET
REDUCING COUPLING
1" x 1/2" M.I. CLASS 150
5/8" (15.9 mm)
w/ GROOVED
1" STEEL PIPE
WALL THICKNESS
RESULTS IN DEFLECTOR-
4" (101.6 mm) TO 12" (304.8 mm)
TO-CEILING DISTANCE OF
4-1/2" (114.3 mm) TO
12-1/2" (317.5 mm)
*
w/ ESCUTCHEON
MODEL S102
WATERWAY
OF SPRINKLER
CENTERLINE
FINISHED
CEILING
*
w/ SET SCREWS
RETAINING
FLANGE
GROMMET
#1781 CENTERING
#1780
2" SCH. 40
(LENGTH TO SUIT
STEEL PIPE SLEEVE
WALL THICKNESS)
OR 2" (50 mm) I.D.
CORED HOLE
END