background image

sign. When installed properly, the Institutional Escutch-
eon is held fast to the mounting surface by the tightening
of the sprinkler assembly into the sprinkler fitting. In order
to accomplish a proper installation, the sprinkler fitting
must be properly located with respect to distance from
the face of the sprinkler fitting to the face of the mounting
surface (Ref. Figure 2); the sprinkler fitting being rigidly
secured and held immobile; and, the centerline of the
sprinkler fitting being perpendicular to the mounting sur-
face to assure that the escutcheon sits squarely against
the mounting surface around the entire perimeter of the
Institutional Escutcheon.

INSTALLATION

The 5.6 K-Factor, StarMax S100 Sprinklers must be in-
stalled in accordance with the following instructions:

NOTES

Refer to the Design Criteria section for important informa-
tion regarding the piping installation design and its affect
on maintaining the integrity of the tamper resistant design
of the Institutional Escutcheons.

If the bulb within the linkage mechanism is cracked or
there is a loss of liquid from the bulb, do not install the
sprinkler. With the bulb in the horizontal position, an air
bubble of approximately 1/16 inch (1,6 mm) diameter
should be present.

A leak tight 1/2 inch NPT sprinkler joint should be ob-
tained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A
maximum of 21 ft.lbs. (28,5 Nm) of torque is to be used to
install these sprinklers. Higher levels of torque may dis-
tort the sprinkler inlet with consequent leakage or impair-
ment of the sprinkler.

Do not attempt to compensate for improper location of
the sprinkler fitting by under- or over-tightening the Sprin-
kler. Readjust the position of the sprinkler fitting to suit, or

increase or decrease the number of #1752 Spacers, as
applicable.

After the installation is complete, make certain that the In-
stitutional Escutcheon is held fast to the mounting sur-
face and that it sits squarely against the ceiling around its
entire perimeter.

1. The S100 Sprinklers must be installed pendent and with

the centerline of their waterway perpendicular to the ceil-
ing.

2. With the Institutional Escutcheon in place and with pipe

thread sealant applied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.

3. Wrench tighten the Sprinkler using only the #1509-1 or

#1509-3 Sprinkler Wrench (Ref. Figure 4). The wrench-
ing teeth of the Sprinkler Wrench are to be applied to
the sprinkler wrenching notch areas (Ref. Figure 1).

4 After the installation is complete, make certain that the

Institutional Escutcheon is held fast to the mounting sur-
face and that it sits squarely against the ceiling around
its entire perimeter.

CARE AND MAINTENANCE

The 5.6 K-Factor, StarMax S100 Sprinklers must be main-
tained and serviced in accordance with the following in-
structions:

NOTES

Service inspections should be made on a regular basis to
detect possible damage or alterations to the sprinkler and
escutcheon. Inspections should include making certain
that the Institutional Escutcheon is held fast to the mount-
ing surface. Damaged or altered sprinklers are to be re-
placed immediately to avoid personal injury and to pre-
vent use for causing personal injury, as well as to
maintain the sprinkler system in an operative condition.

Before closing a fire protection system main control valve
for maintenance work on the fire protection system which
it controls, permission to shut down the affected fire pro-
tection systems must be obtained from the proper authori-
ties and all personnel who may be affected by this action
must be notified.

Sprinklers which are found to be leaking or exhibiting vis-
ible signs of corrosion must be replaced.

Automatic sprinklers must never be shipped or stored
where their temperatures will exceed 100°F/38°C and
they must never be painted, plated, coated, or otherwise
altered after leaving the factory. Modified or over-heated
sprinklers must be replaced.

Care must be exercised to avoid damage to the sprinklers
- before, during, and after installation. Sprinklers dam-
aged by dropping, striking, wrench twist/slippage, or the
like, must be replaced. Also, replace any sprinkler that
has a cracked bulb or that has lost liquid from its bulb
(ref. Installation Section).

The owner is responsible for the inspection, testing, and

STAR SPRINKLER

Page 2

1-5.2.11

FIGURE 1

5.6 K-FACTOR, STARMAX S100 QUICK RESPONSE

INSTITUTIONAL PENDENT SPRINKLER

3.18"

(80.8 mm)

FITTING

FACE OF

SPRINKLER

SPRINKLER

NOTCH (2)

WRENCHING

IN OPERATED

DEFLECTOR

POSITION

(80.0 mm)

NPT

3.15"

1/2"

7/16" (11.1 mm)

NOMINAL MAKE-IN

OBSOLETE

Содержание Star StarMax S100

Страница 1: ...ement is protected within the link age mechanism of the StarMax The bulb contains a fluid which expands when exposed to heat When the rated temperature is reached the fluid expands sufficiently to shatter the glass bulb Shattering of the glass bulb re leases the linkage mechanism holding the sprinkler closed which then allows the sprinkler to activate by al lowing the deflector to extend downward ...

Страница 2: ...nt applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting 3 Wrench tighten the Sprinkler using only the 1509 1 or 1509 3 Sprinkler Wrench Ref Figure 4 The wrench ing teeth of the Sprinkler Wrench are to be applied to the sprinkler wrenching notch areas Ref Figure 1 4 After the installation is complete make certain that the Institutional Escutcheon is held fast to the mou...

Страница 3: ...ARMAX S100 22 2 mm 1751 5 STYLE E UP TO 1752 SPACERS THREE WITH 3 SPACERS WITH NO SPACERS DIAMETER DETERMINED REDUCING COUPLING BY CLEARANCE FOR 127 0 mm THREE SPACERS 1752 UP TO 1 7 16 36 5 mm 1 2 1751 4 STYLE D 1 13 28 7 mm MIN 1 80 45 7 mm MIN 2 02 51 3 mm MAX 5 DIA 1 2 7 8 1 35 34 3 mm MAX 2 1 1 42 36 1 mm MIN 1 65 41 9 mm MAX 1 50 38 1 mm MIN 1 73 43 9 mm MAX WITH NO SPACERS WITH 3 SPACERS 12...

Страница 4: ...sign errors or inaccurate or incomplete information supplied by Buyer or Buyer s representatives IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI ABLE IN CONTRACT TORT STRICT LIABILITY OR UN DER ANY OTHER LEGAL THEORY FOR INCIDENTAL INDIRECT SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LABOR CHARGES REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMA...

Отзывы: