Quick Response - Std. Coverage
Hor. Sidewall Sprinklers and
Rec. Hor. Sidewall Sprinklers
Star Galaxy™ SGQR, K=4.2 and 5.6

GENERAL DESCRIPTION

The Star Galaxy SGQR, 4.2 and 5.6 K-Factor, Horizontal
Sidewall and Recessed Horizontal Sidewall Sprinklers
are quick response - quick coverage, decorative glass
bulb type spray sprinklers designed for use in commer-
cial occupancies such as banks, hotels, office buildings,
etc. They are designed for installation along a wall or the
side of a beam and just beneath a smooth ceiling. Hori-
zontal sidewall sprinklers are commonly used instead of
pendent or upright sprinklers because of aesthetics or
building construction considerations, where piping across
the ceiling is not desirable.

The recessed version of the Star Galaxy SG, intended for
use in areas with concealed piping and a finished wall,
uses a two-piece #2084 or #2085 Recessed Escutcheon.
The #2084 provides 1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of total adjustment from
the flush sidewall position, and the #2085 provides 1/2
inch (12,7 mm) of recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the flush sidewall posi-
tion. The adjustment provided by the Recessed Escutch-
eon reduces the accuracy to which the fixed pipe nipples
to the sprinklers must be cut.

Lead coatings are utilized to extend the life of copper al-
loy sprinklers beyond that which would otherwise be ob-
tained when exposed to corrosive atmospheres. Although
lead coated sprinklers have passed the standard corro-
sion tests of the applicable approval agencies, the testing
is not representative of all possible corrosive atmos-
pheres. Consequently, it is recommended that the end
user be consulted with respect to the suitability of these
corrosion resistant coatings for any given corrosive envi-
ronment. The effects of ambient temperature, concentra-
tion of chemicals, and gas/chemical velocity, should be
considered, as a minimum, along with the corrosive na-
ture of the chemical to which the sprinklers will be ex-
posed.

WARNINGS

The Star Galaxy SGQR Sprinklers described herein must
be installed and maintained in compliance with this docu-
ment, as well as with the applicable standards of the Na-
tional Fire Protection Association, in addition to the stand-
ards of any other authorities having jurisdiction. Failure to
do so may impair the integrity of these devices.

The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.

OPERATION

The glass bulb contains a fluid which expands when ex-
posed to heat. When the rated temperature is reached,
the fluid expands sufficiently to shatter the glass bulb,
which then allows the sprinkler to activate and flow water.

TECHNICAL DATA

Approvals

UL and ULC Listed. FM and NYC Approved.
(Refer to Table A. The approvals apply only to the service
conditions indicated in the Design Criteria section.)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

1/2 inch NPT

Discharge Coefficient

K = 4.2 GPM/psi

1/2

(60,5 LPM/bar

1/2

)

K = 5.6 GPM/psi

1/2

(80,7 LPM/bar

1/2

)

Temperature Ratings

135°F/57°C, 155°F/68°C, 175°F/79°C,
200°F/93°C, or 286°F/141°C
(Refer to Table A)

Finishes

Sprinkler: White Polyester, Black Polyester,
Chrome Plated, Natural Brass,
Lead Coated (Refer to Table A)
Recessed Escutcheon: White Coated, Black Coated,
Chrome Plated, Bright Brass Plated
(Other colors are available on request.)

Physical Characteristics (Ref. Figure 1)

The Star Galaxy SGQR utilizes a dezincification resistant
(DZR) bronze frame, and a 3 mm diameter glass bulb.
The two-piece button assembly is brass and copper. The
gasketed spring plate consists of a beryllium nickel disc
spring that is sealed on both its inside and outside edges
with a Teflon

†

gasket. The compression screw is bronze,

and the deflector is brass.

SIN S2977

4.2 K-Factor

SIN S2973

5.6 K-factor

Shown With

#2085 Recessed

Escutcheon

D

uP

ont

Reg

is

ter

ed

Tr

ademar

k

Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500

3-01

1-1.3.11

TYCO FIRE PRODUCTS

OBSOLETE

Содержание Star Galaxy SGQR

Страница 1: ...chemical to which the sprinklers will be ex posed WARNINGS The Star Galaxy SGQR Sprinklers described herein must be installed and maintained in compliance with this docu ment as well as with the applicable standards of the Na tional Fire Protection Association in addition to the stand ards of any other authorities having jurisdiction Failure to do so may impair the integrity of these devices The o...

Страница 2: ...m of torque may be used to install sprinklers with 1 2 NPT connections Higher lev els of torque may distort the sprinkler inlet with conse quent leakage or impairment of the sprinkler Do not attempt to make up for insufficient adjustment in the escutcheon plate by under or over tightening the STAR SPRINKLER Page 2 1 1 3 11 FIGURE 2 4 2 and 5 6 K FACTOR STAR GALAXY SGQR HORIZONTAL SIDEWALL SPRINKLE...

Страница 3: ...F 93 C Green 286 F 141 C Blue Lead Coated Polyester Coated All Colors SPRINKLER FINISH 5 6 K Factor Recessed Horizontal Sidewall S2973 With 2084 Escutcheon Temperature Rating Bulb Liquid Code Natural Brass Chrome Plated Polyester Coated All Colors 1 2 3 4 1 2 3 4 1 2 135 F 57 C Orange 155 F 68 C 175 F 79 C Red Yellow 200 F 93 C Green SPRINKLER FINISH 4 2 K Factor Horizontal Sidewall S2977 Temperat...

Страница 4: ...and all personnel who may be affected by this action must be notified Absence of an escutcheon which is used to cover a clear ance hole may delay the time to sprinkler operation in a fire situation Sprinklers which are found to be leaking or exhibiting vis ible signs of corrosion must be replaced Automatic sprinklers must never be shipped or stored where their temperature will exceed 100 F 38 C an...

Страница 5: ...oducts Tyco Fire Products shall not be responsible for sprinkler sys tem design errors or inaccurate or incomplete information supplied by Buyer or Buyer s representatives IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI ABLE IN CONTRACT TORT STRICT LIABILITY OR UN DER ANY OTHER LEGAL THEORY FOR INCIDENTAL INDIRECT SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LABOR CHARGES REGARDLESS OF...

Страница 6: ...STAR SPRINKLER Page 6 1 1 3 11 7071 S 13th Street Suite 103 Oak Creek WI 53154 www starsprinkler com PRINTED IN U S A 3 01 O B S O L E T E ...

Отзывы: