background image

DESIGN CRITERIA

The Star Galaxy SG-R (SIN S2287) Residential Pendent
and Recessed Pendent Sprinklers must only be installed
and utilized in accordance with the following described cri-
teria which are provided by the manufacturer.

NOTES

Residential Fire Sprinkler Systems should only be de-
signed and installed by those competent and com-
pletely familiar with automatic sprinkler system de-
sign, installation procedures, and techniques.

Several criteria may apply to the installation and us-
age of each sprinkler. Consequently, it is recom-
mended that the sprinkler system designer review
and develop a working understanding of the com-
plete list of criteria prior to initiating the design of the
sprinkler system.

Questions concerning sprinkler installation and usage
criteria which are not covered by the following instruc-
tions should be submitted to Technical Services. In-
clude sketches and technical details as appropriate.

In some instances, the requirements of this docu-
ment may concern specifications which are more
stringent and which take precedence over those
specified in NFPA 13, NFPA 13D, NFPA 13R, or by the
authority having jurisdiction.

The spray from the sprinkler is distributed radially
outward and downward from the sprinkler deflector.
Consequently, the sprinklers must be located such
that there will not be any blind spaces shielded from
spray by partitions, room dividers, overhangs or
other parts of the dwelling structure.

The number of sprinklers within each compartment
(as defined by NFPA 13, 13D, or 13R), must be kept
as few as possible. Do NOT use more sprinklers than
necessary to cover a particular space.

Use only metallic sprinkler escutcheons that will not
dislodge or deform at a temperature less than
1200°F/649°C or that are UL Listed for fire protection
service. Use only the #2084 Recessed Escutcheon for
recessed installations.

The sprinkler must be secured in position by firmly
fastening the sprinkler system piping to the struc-
ture. If the sprinkler is not properly secured in posi-
tion, reaction forces resulting from sprinkler opera-
tion could alter its orientation and its water
distribution pattern. The sprinkler escutcheon cannot
be used to hold the sprinkler in position.

General Service Conditions.

The Star Galaxy SG-R

must only be utilized in wet pipe sprinkler systems.

Hydraulic Design Criteria.

The minimum required flow

rates for residential applications are given in Table A as a
function of the maximum allowable coverage areas. The
NFPA 13D/13R single sprinkler flow rate is the minimum
required discharge from the most hydraulically demand-
ing single sprinkler and the NFPA 13D/13R multiple sprin-
kler flow rate is the minimum required discharge from
each of the total number of “design sprinklers” as speci-
fied in NFPA 13D or 13R.

TIA 99-1 (Tentative Interim Amendment) with an effective
date of May 22, 2000 states that the minimum required
discharge from each of the “design sprinklers” for sys-
tems designed to NFPA 13 must be calculated based on

delivering a minimum design density of 0.1 gpm/sq. ft. for
each of the listed coverage areas shown in Table A. Con-
sult with the Authority Having Jurisdiction regarding the
application of this TIA to the currently adopted NFPA 13.

For systems designed to NFPA 13, 13D, or 13R, consult
with the local authority having jurisdiction with regard to
the number of “design sprinklers” for sloped ceilings hav-
ing a slope greater than a 2 inch rise for a 12 inch run.

Spray Coverage Criteria.

Figures 5 through 9 provide

spacing rules that must be followed to assure that the
Star Galaxy SG-R Sprinklers will provide their design dis-
tribution of water spray.

Operational Sensitivity Criteria.

For proper operational

sensitivity, the Star Galaxy SG-R must be installed be-
neath a solid ceiling having a smooth or textured surface.
The deflector-to-ceiling distance is to be 1-1/2 to 4
inches, unless a #2084 Recessed Escutcheon is being
utilized per Figure 2.

The Star Galaxy SG-R must

NOT

be used above or be-

low open-gridded type suspended ceilings; beneath sof-
fits or beams resulting in a deflector-to-ceiling distance
(i.e., deflector-to-mounting surface plus depth of soffit or
beam) exceeding 4 inches; or, with beams, joists, or
ducts having a height of more than 3 inches located
within the sprinkler coverage areas. Beams having a
height of more than 3 inches may be located with their
centerlines along the boundaries separating adjacent
sprinkler coverage areas.

Cold Soldering Criteria.

Figures 5 and 6 provide the

minimum spacing requirements necessary for preventing

STAR SPRINKLER

Page 2

1-3.2.10

†

DuPont Registered Trademark

(a) For coverage area dimensions less than or between those

indicated, it is necessary to use the minimum required flow for
the next highest coverage area for which hydraulic design
criteria are stated.

(b) Requirement is based on minimum flow in GPM from each

sprinkler. The associated residual pressures are calculated
using the nominal K-factor. Refer to Hydraulic Design Criteria
Section for details.

TABLE A

HYDRAULIC DESIGN CRITERIA

12 x 12

MAXIMUM

COVERAGE

AREA

(a)

FT. x FT.

Recessed

NFPA 13D/13R

MINIMUM SINGLE

SPRINKLER

FlOW

(b)

14 x 14

16 x 16

18 x 18

20 x 20

16 GPM

(13.8 PSI)

11.4 GPM

(7.0 PSI)

17 GPM

(15.6 PSI)

13 GPM

(9.1 PSI)

19 GPM

(19.5 PSI)

14 GPM

(10.6 PSI)

20 GPM

(21.6 PSI)

17 GPM

(15.6 PSI)

16 GPM

(13.8 PSI)

11.4 GPM

(7.0 PSI)

Pendent

NFPA 13D/13R

MINIMUM MULTIPLE

SPRINKLER

FLOW

(b)

Pendent

Recessed

13 GPM

(9.1 PSI)

16 GPM

(13.8 PSI)

17 GPM

(15.6 PSI)

17 GPM

(15.6 PSI)

21 GPM

(23.9 PSI)

11.4 GPM

(7.0 PSI)

11.4 GPM

(7.0 PSI)

13 GPM

(9.1 PSI)

13 GPM

(9.1 PSI)

17 GPM

(15.6 PSI)

OBSOLETE

Содержание Star Galaxy SG-R

Страница 1: ...he above cited stipulations and the var ied nature of residential type architecture there will be some compartment designs which cannot be fully sprinklered in accordance with the recommendations of N...

Страница 2: ...rge from each of the total number of design sprinklers as speci fied in NFPA 13D or 13R TIA 99 1 Tentative Interim Amendment with an effective date of May 22 2000 states that the minimum required disc...

Страница 3: ...r tight ening the Sprinkler Readjust the position of the sprin kler fitting to suit 1 The sprinkler must only be installed in the pendent position and with the deflector parallel to the mounting surfa...

Страница 4: ...STAR SPRINKLER Page 4 1 3 2 10 FIGURE 5 PLAN VIEW ILLUSTRATIONS OF SPRINKLER TO WALL AND SPRINKLER TO SPRINKLER POSITIONING O B S O L E T E...

Страница 5: ...IRED HORIZONTAL DISTANCE BETWEEN TWO SPRINKLERS LOCATED ON THE SAME ELEVATION ON OPPOSING SLOPED CEILINGS FIGURE 7 MAXIMUM PERMITTED VERTICAL DISTANCE BETWEEN THE SPRINKLER DEFLECTOR AND THE BOTTOM OF...

Страница 6: ...EQUIRED HORIZONTAL DISTANCE BETWEEN A SPRINKLER LOCATED ON A LEVEL CEILING AND AN INTERSECTING SLOPED CEILING FIGURE 9 MINIMUM REQUIRED SLANT DISTANCE BETWEEN A LEVEL CEILING AND A SPRINKLER LOCATED O...

Страница 7: ...be painted plated coated or otherwise al tered after leaving the factory Modified sprinklers must be replaced Sprinklers that have been exposed to corro sive products of combustion but have not operat...

Страница 8: ...le of products or parts of products Tyco Fire Products shall not be responsible for sprinkler sys tem design errors or inaccurate or incomplete information supplied by Buyer or Buyer s representatives...

Отзывы: