Tyco Fire Product Star E Скачать руководство пользователя страница 3

STAR SPRINKLER

1-1.3.30

Page 3

SPRINKLER FINISH

Temperature

Rating

Frame

Color Code

Natural

Brass

Chrome

Plated

135°F/57°C

165°F/74°C

212°F/100°C

Unpainted

White

Unpainted

1, 2, 4

Notes:

1. Listed by Underwriters Laboratories, Inc. for Light and Ordinary Hazard Occupancies.
2. Listed by Underwriters’ Laboratories of Canada for Light Hazard Occupancies.
3. Approved by Factory Mutual Research Corporation for Light Hazard Occupancies.
4. Approved by the City of New York under MEA 395-91-M.

TABLE A

LABORATORY LISTINGS AND APPROVALS

280°F/138°C

Blue

360°F/182°C

Red

Natural

Brass

Chrome

Plated

K=5.6 in Upright Position

(S5002)

1, 2, 3, 4

2, 4

400°F/204°C

520°F/271°C

Green

Orange

K=8.0 in Pendent Position

(S5009)

SPRINKLER FINISH

K=8.0 in Upright Position

(S5009)

Temperature

Rating

Frame

Color Code

Natural

Brass

Chrome

Plated

Natural

Brass

Chrome

Plated

135°F/57°C

Unpainted

165°F/74°C

Unpainted

212°F/100°C

White

280°F/138°C

Blue

360°F/182°C

Red

400°F/204°C

Green

520°F/271°C

Orange

1, 2, 4

1, 4

K=5.6 in Pendent Position

(S5002)

OBSOLETE

Содержание Star E

Страница 1: ... to any questions OPERATION A bronze tube sealed by a steel ball holds a fusible alloy The tube is compression loaded and via the tension mechanism the cap seals the sprinkler orifice When the rated temperature is reached the alloy melts the ball is forced inward and the tension mechanism releases the cap which then allows the sprinkler to activate and flow water TECHNICAL DATA Approvals UL and UL...

Страница 2: ... with a torque of 10 to 20 ft lbs 13 6 to 27 1 Nm A maximum of 30 ft lbs 40 7 Nm of torque may be used to install sprinklers with 3 4 NPT connections Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler 1 The Model E Vertical Sidewall Sprinklers may be installed in either the pendent or upright position and the flow Ref Figure 1 or 2 is to ...

Страница 3: ...d Occupancies 4 Approved by the City of New York under MEA 395 91 M TABLE A LABORATORY LISTINGS AND APPROVALS 280 F 138 C Blue 360 F 182 C Red Natural Brass Chrome Plated K 5 6 in Upright Position S5002 1 2 3 4 2 4 400 F 204 C 520 F 271 C Green Orange K 8 0 in Pendent Position S5009 SPRINKLER FINISH K 8 0 in Upright Position S5009 Temperature Rating Frame Color Code Natural Brass Chrome Plated Nat...

Страница 4: ...arranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Prod ucts or for products and components which have been subject to misuse improper installation corrosion or which have not been installed maintained modified or re paired in accordance with applicable Standards of the Na tional Fire Protection Association and or the standards of any o...

Отзывы: