Tyco Fire Product Gem TY-B Скачать руководство пользователя страница 5

spected and the wax coating re-
touched (repaired) whenever the coat-
ing has been damaged and bare metal
is exposed. The wax coating on the
wrench flats can be retouched by gen-
tly applying a heated 1/8 inch diameter
steel rod to the areas of wax that have
been damaged, to smooth it back over
areas where bare metal is exposed.

NOTES

Only retouching of the wax coating ap-
plied to the  wrench  flats and  frame
arms is permitted, and the retouching
is to be performed only at the time of
the initial sprinkler installation.

The steel rod should be heated only to
the point at which it can begin to melt

the wax, and appropriate precautions
need to be taken, when handling the
heated rod, in order to prevent the
installer from being burned.

If attempts to retouch the wax coating
with complete  coverage are unsuc-
cessful, additional wax can be ordered
in the form of a wax stick (the end of
which is color coded). Only the correct
color coded wax is to be used, and
retouching of wrench flats and frame
arms is only permitted at the time of
initial sprinkler installation. With the
steel rod heated as previously de-
scribed, touch the rod to the area re-
quiring additional wax with the rod an-
gled downward, and  then touch the
wax stick to the rod approximately
one-half inch away from the area re-
quiring retouching. The wax will melt
and run down onto the sprinkler.

The

Series TY-B Recessed Pendent

Sprinklers

must be installed  in  ac-

cordance with the  following instruc-
tions.

Step A.

After installing the Style 10 or

40 Mounting Plate, as applicable, over
the sprinkler threads and with pipe

TFP151

Page 5 of 8

FIGURE 4

SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY

WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT

STYLE 10 RECESSED ESCUTCHEON

5.6 K-FACTOR, 1/2 INCH NPT

(57,2 mm)

2-1/4" DIA.

(73,0 mm)

2-7/8" DIA.

SPRINKLER

MOUNTING

CLOSURE

SURFACE

FACE OF

FITTING

(15,9±6,4 mm)

5/8±1/4"

(3,2 mm)

3/4" (19,1 mm)

1-1/4" (31,8 mm)

PLATE

MOUNTING

1/8"

1/4" (6,4 mm)

3/4" (19,1 mm)

SERIES

TY-B

FIGURE 6

W-TYPE 6 SPRINKLER

WRENCH

WRENCH RECESS

(END "A" USED FOR

1/2" NPT MODELS)

WRENCH RECESS

(END "B" USED FOR

3/4" NPT MODELS)

FIGURE 7

W-TYPE 7 RECESSED

SPRINKLER WRENCH

RECESS

WRENCH

WITH SPRINKLER

ENGAGEMENT

IN TO ENSURE

WRENCHING AREA

PUSH WRENCH

FIGURE 5

SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY

WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT

STYLE 40 RECESSED ESCUTCHEON

8.0 K-FACTOR, 3/4 INCH NPT

2-7/8" DIA.

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

MOUNTING

SPRINKLER

CLOSURE

SURFACE

FITTING

FACE OF

(15,9±6,4 mm)

5/8±1/4"

MOUNTING

PLATE

1-5/16" (33,3 mm)

13/16" (20,6 mm)

(3,2 mm)

1/8"

3/4" (19,1 mm)

1/4" (6,4 mm)

SERIES

TY-B

OBSOLETE

Содержание Gem TY-B

Страница 1: ...te level version of the Series TY B Pendent Sprinkler can be obtained by utilizing the Series TY B Pendent Sprinkler in combination with the Model S2 Shield WARNINGS The Series TY B Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the standards of any ...

Страница 2: ... orifice seat on frame Pipe thread connections per ISO 7 1 can be provided on special request 2 4 5 6 PENDENT CROSS SECTION 58 7 mm 2 5 16 39 7 mm 1 9 16 PLATE SEATING ESCUTCHEON 1 2 12 7 mm NOMINAL MAKE IN SURFACE 1 3 NPT 3 4 RECESSED PENDENT UPRIGHT 12 7 mm NOMINAL MAKE IN 1 2 RECESSED STYLE 40 ESCUTCHEON 57 2 mm 2 1 4 3 4 NPT DEFLECTOR SSU SSP DEFLECTOR 7 FLATS WRENCH 2 7 8 73 0 mm DIA FIGURE 2...

Страница 3: ...position of the sprinkler fitting to suit The Series TY B Pendent and Up right Sprinklers must be installed in accordance with the following instruc tions Step 1 Pendent sprinklers are to be installed in the pendent position and upright sprinklers are to be installed in the upright position Step 2 With pipe thread sealant ap plied to the pipe threads hand tighten the sprinkler into the sprinkler f...

Страница 4: ...orrosion Resistant Sprinklers Installed with Style 10 1 2 NPT or Style 40 3 4 NPT 3 4 Total Adjustment Recessed Escutcheon as applicable 150 F 66 C Maximum Ceiling Temperature White or Any Color Frame and Deflector only N A Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 1 2 5 WAX OVER LEAD COATED LEAD COATED WAX COATED N A 1 2 3 5 1 2 3 5 1 2 3 5 1 2 3 5 1 2 3 5 N A 5 6 1 2 NPT PENDENT TY...

Страница 5: ...gled downward and then touch the wax stick to the rod approximately one half inch away from the area re quiring retouching The wax will melt and run down onto the sprinkler The Series TY B Recessed Pendent Sprinklers must be installed in ac cordance with the following instruc tions Step A After installing the Style 10 or 40 Mounting Plate as applicable over the sprinkler threads and with pipe TFP1...

Страница 6: ...pec tions should be made so as to better determine the exact sprinkler condi tion and the long term integrity of the corrosion resistant coating as it may be affected by the corrosive conditions present The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards of the N...

Страница 7: ...ify Specify color color coded Wax Stick for retouching specify tem perature rating temperature rated Se ries TY B Sprinklers P N specify Black for 135 F P N 56 065 1 135 Red for 155 F P N 56 065 1 155 Yellow for 175 F P N 56 065 1 175 Blue for 200 F and 286 F P N 56 065 1 286 NOTES Each wax stick is suitable for retouch ing up to twenty five sprinklers The wax used for 286 F sprinklers is the same...

Страница 8: ...Page 8 of 8 TFP151 TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale Pennsylvania 19446 O B S O L E T E ...

Отзывы: