background image

Care and
Maintenance

The Series TY-B Sprinklers must be
maintained and  serviced in accord-
ance with the following instructions:

NOTES

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.

Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.

Automatic sprinklers must  never be
shipped or stored where their tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated
or otherwise altered after leaving the
factory. Modified sprinklers must be re-
placed. Sprinklers that have been ex-
posed to corrosive products of com-
bustion, but have not operated, should
be  replaced  if  they cannot  be  com-
pletely cleaned by wiping the sprinkler
with a cloth or by brushing it with a soft
bristle brush.

Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost

liquid from its bulb. (Ref. Installation
Section).

Frequent  visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after  the  installation has  been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in  compliance with this  docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.

It is recommended that automatic
spr inkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Limited
Warranty

Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty

is

given

for

products

or

components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-

TFP661

Page 3 of 4

TYPE

TEMP.

BULB

LIQUID

NATURAL

BRASS

CHROME

PLATED

135°F/57°C

286°F/141°C

360°F/182°C

5.6K

CONVENTIONAL

(TY3651)

or

8.0K

CONVENTIONAL

(TY4651)

SPRINKLER FINISH (See Note 5)

1, 2, 3, 4

Orange

Red

Yellow

Green

Blue

Mauve

155°F/68°C

175°F/79°C

200°F/93°C

NOTES:

1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
3. Approved by the Loss Prevention Certification Board (LPCB).
4. Approved by the City of New York under MEA 354-01-E.
5. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed, the

sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers.

** 150°F/66°C Maximum Ceiling Temperature.
*** White or Any Color (Frame and Deflector only).
N/A: Not Available

TABLE A

LABORATORY LISTINGS AND APPROVALS

WAX OVER

LEAD COATED

LEAD

COATED

WAX

COATED

1, 2, 4

1, 2, 4

1**, 2**, 4**

1**, 2**, 4**

1, 2, 4

N/A

POLYESTER

COATED***

OBSOLETE

Отзывы: