background image

APPROVALS AND STANDARDS

The Model TFP1 Residential Flush
Pendent Sprinklers are listed by Un-
derwriter’s Laboratories, Inc. (UL) and
by Underwriters Laboratories, Inc. for
use in Canada (C-UL) under the name
of Tyco Fire Products. With exception
to the sloped ceiling criteria, the ap-
provals only apply to the service con-
ditions indicated in the design Criteria
section.

WARNINGS

The Model TFP1 Residential

Flush Pendent Sprinklers de-

scribed herein must be installed

and maintained in compliance

with this document, as well as

with the applicable standards of

the National Fire Protection As-

sociation, in addition to the

standards of any other authori-

ties having jurisdiction. Failure

to do so may impair the integrity

of these devices.

Because of the above cited stipu-

lations and the varied nature of

residential type architecture,

there will be some compartment

designs which cannot be fully

sprinklered in accordance with

the recommendations of NFPA 13,

13D, or 13R. In the event of this

condition, consult the authorities

having jurisdiction for guidance

and approval.

It is the responsibility of the in-

stalling contractor to provide a

copy of this document to the

owner or his representative, and

in turn, it is the obligation of the

owner to provide a copy of this

document to a succeeding owner.

The owner is responsible for

maintaining their fire protection

system and devices in proper op-

erating condition. The installing

contractor or sprinkler manufac-

turer should be contacted relative

to any questions.

TECHNICAL DATA

Maximum Working Pressure:

175 psi (12,1 bar)

Discharge Coefficient:

K = 4.2 GPM/psi

1/2

(60,5 LPM/bar

1/2

)

Temperature Rating:

162°F/72°C

Adjustment:

3/8 inch (9,5 mm) vertical

Finishes:

Sprinkler and Escutcheon:
White, Chrome

Physical Characteristics:

Dezincification bronze body and cop-
per gasketed orifice seal design.

DESIGN CRITERIA

The Model TFP1 Residential Flush
Pendent Sprinklers must only be in-
stalled and utilized in accordance with
the following described criteria which
are provided by the manufacturer.

NOTES

Residential Fire Sprinkler Sys-

tems should only be designed and

installed by those competent and

completely familiar with auto-

matic sprinkler system design, in-

stallation procedures, and tech-

niques.

Several criteria may apply to the

installation and usage of each

sprinkler. Consequently, it is rec-

ommended that the sprinkler sys-

tem designer review and develop

a working understanding of the

complete list of criteria prior to

initiating the design of the sprin-

kler system.

Questions concerning sprinkler

installation and usage criteria

which are not covered by the fol-

lowing instructions should be

submitted to Tyco Fire Products

Include sketches and technical

details as appropriate.

In some instances, the require-

ments of this document may con-

cern specifications which are

more stringent and which take

precedence over those specified in

NFPA 13, NFPA 13D, NFPA 13R,

or by the authority having juris-

diction.

The spray from the sprinkler is

distributed radially outward and

downward from the sprinkler de-

flector. Consequently, the sprin-

klers must be located such that

there will not be any blind spaces

shielded from spray by partitions,

room dividers, overhangs or other

parts of the dwelling structure.

The number of sprinklers within

each compartment (as defined by

NFPA 13, 13D, or 13R), must be

kept as few as possible. Do NOT

use more sprinklers than neces-

sary to cover a particular space.

Use only the escutcheon provided

with the Model TFP1.

The sprinkler must be secured in

position by firmly fastening the

sprinkler system piping to the

structure. If the sprinkler is not

properly secured in position, re-

action forces resulting from

sprinkler operation could alter

its orientation and its water dis-

tribution pattern. The sprinkler

escutcheon cannot be used to hold

the sprinkler in position.

General Service Conditions.

The

Model TFP1 must only be utilized in
wet pipe sprinkler systems.

Hydraulic Design Criteria.

The mini-

mum required single and multiple

TABLE A

NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA

(a) For coverage area dimensions less than or between those indicated, it is
necessary to use the minimum required flow for the next highest coverage area
for which hydraulic design criteria are stated.

(b) Requirement is based on minimum flow in GPM from each sprinkler. The
associated residual pressures are calculated using the nominal K-factor. Refer to
Hydraulic Design Criteria Section for details.

12 x 12

MAXIMUM

COVERAGE

AREA

(a)

FT. x FT.

SINGLE

SPRINKLER

Minimum Flow

(b)

Residual Pressure

14 x 14

16 x 16

18 x 18

20 x 20

11.5 GPM (43,5 LPM)

7.5 PSI (0,5 BAR)

11.5 GPM (43,5 LPM)

7.5 PSI (0,5 BAR)

14 GPM (53,0 LPM)

11.1 PSI (0,8 BAR)

14 GPM (53,0 LPM)

11.1 PSI (0,8 BAR)

18 GPM (68,1 LPM)

18.4 PSI (1,3 BAR)

16 GPM (60,6 LPM)

14.5 PSI (1,0 BAR)

23 GPM (87,1 LPM)

30.1 PSI (2,1 BAR)

20 GPM (75,7 LPM)

22.7 PSI (1,6 BAR)

11.5 GPM (43,5 LPM)

7.5 PSI (0,5 BAR)

11.5 GPM (43,5 LPM)

7.5 PSI (0,5 BAR)

162°F

MULTIPLE

SPRINKLERS

Minimum Flow

(b)

Residual Pressure

162°F

-2-

OBSOLETE

Close

Содержание Gem TFP1

Страница 1: ...cal ad justment This adjustment reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut to help assure a perfect fit installation The Model TFP1 has been designed with heat se...

Страница 2: ...rking understanding of the complete list of criteria prior to initiating the design of the sprin kler system Questions concerning sprinkler installation and usage criteria which are not covered by the...

Страница 3: ...lers with respect to obstructions to water distribution are to be in accordance with the obstruction rules for extended coverage pendent sprinklers per the requirements of NFPA 13 Operational Sensitiv...

Страница 4: ...orizontal b the compartment openings to adjoining spaces have minimum lintel depths of 8 inches below the lowest sprinkler c any adjacent sprinklers in the direction of the ceiling ridge are to be in...

Страница 5: ...6 After the ceiling has been com pleted with the 2 inch 50 mm diame ter clearance hole use the Protective Cap Removal Tool Ref Figure 5 to remove the Protective Cap and then push on the Escutcheon unt...

Страница 6: ...Buyer for ten 10 years against defects in material and work manship when paid for and properly installed and maintained under normal use and service This warranty will ex pire ten 10 years from date...

Страница 7: ...G THE WATER DISTRIBUTION LOCATED ON AN INTERSECTING PITCHED CEILING COVERAGE AREAS a 20 x 20 c 16 x 16 b 18 x 18 d 14 x 14 d 12 x 12 GRAPH A MINIMUM REQUIRED HORIZONTAL DISTANCE BETWEEN A SPRINKLER LO...

Страница 8: ...IS LOCATED AT A PEAK NOTES UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED THE MOUNTING SURFACE MUST BE LOCATED WITHIN 4 TO 6 INCHES OF THE PEAK IF IT IS NOT...

Отзывы: