RESIDENTIAL SPRINKLERS

FLUSH PENDENT
Model TFP1, K=4.2, 162°F/72°C

GENERAL DESCRIPTION

The Model TFP1 Residential Flush
Pendent Sprinklers are decorative fus-
ible solder sprinklers designed for use
in residential occupancies such as
homes, apartments, dormitories, and
hotels. When aesthetics is the major
consideration, the Model TFP1 should
be your first choice.

They are to be used in wet pipe resi-
dential sprinkler systems for one- and
two-family dwellings and mobile
homes per NFPA 13D; wet pipe resi-
dential sprinkler systems for residen-
tial occupancies up to and including
four stories in height per NFPA 13R; or,
wet pipe sprinkler systems for the resi-
dential portions of any occupancy per
NFPA 13.

The Model TFP1 has a 4.2 (60,5) K-
factor which provides very low design
flow rates at reduced residual pres-
sures, enabling smaller pipe sizes and
water supply requirements.

The flush design of the Model TFP1
features a separable escutcheon pro-
viding 3/8 inch (9,5 mm) vertical ad-
justment. This adjustment reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut to help
assure a perfect fit installation.

The Model TFP1 has been designed
with heat sensitivity and water distribu-
tion characteristics proven to help in
the control of residential fires to im-
prove the chance for occupants to es-
cape or be evacuated. However, resi-
dential fire sprinkler systems are not a
substitute for intelligent fire safety
awareness or fire safety construction
required by building codes.

TYCO FIRE PRODUCTS

, 7071 S. 13th Street, Suite 103 Oak Creek, WI 53154 — www.gemsprinkler.com

Customer Service/Sales:

Tel: (877) 436-8926 / Fax: (877) 866-9250

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

FIGURE 1

MODEL TFP1 (SIN TY2264) RESIDENTIAL

FLUSH PENDENT SPRINKLER

A

B

C

SPRINKLER

AREA

WRENCHING

TOLERANCE

CEILING LEVEL

LIMIT

FITTING

FACE OF

SPRINKLER

PROTECTIVE CAP

(23.0±4.8 mm)

29/32±3/16"

MOUNTING

SURFACE

3/32" (2.4 mm) TYP.

2-15/16" (75 mm) DIA.

IN OPERATED

POSITION

DEFLECTOR

29/32±3/16"

(23.0±4.8 mm)

2" (50 mm) DIA.

DO NOT

OVER-TIGHTEN

COLLECTOR

HEAT

(57.2 mm)

2-1/4"

NOMINAL MAKE-IN

7/16" (11.1 mm)

1/2" NPT

Printed in U.S.A. 3-01

TD585A

OBSOLETE

Close

Содержание Gem TFP1

Страница 1: ...cal ad justment This adjustment reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut to help assure a perfect fit installation The Model TFP1 has been designed with heat se...

Страница 2: ...rking understanding of the complete list of criteria prior to initiating the design of the sprin kler system Questions concerning sprinkler installation and usage criteria which are not covered by the...

Страница 3: ...lers with respect to obstructions to water distribution are to be in accordance with the obstruction rules for extended coverage pendent sprinklers per the requirements of NFPA 13 Operational Sensitiv...

Страница 4: ...orizontal b the compartment openings to adjoining spaces have minimum lintel depths of 8 inches below the lowest sprinkler c any adjacent sprinklers in the direction of the ceiling ridge are to be in...

Страница 5: ...6 After the ceiling has been com pleted with the 2 inch 50 mm diame ter clearance hole use the Protective Cap Removal Tool Ref Figure 5 to remove the Protective Cap and then push on the Escutcheon unt...

Страница 6: ...Buyer for ten 10 years against defects in material and work manship when paid for and properly installed and maintained under normal use and service This warranty will ex pire ten 10 years from date...

Страница 7: ...G THE WATER DISTRIBUTION LOCATED ON AN INTERSECTING PITCHED CEILING COVERAGE AREAS a 20 x 20 c 16 x 16 b 18 x 18 d 14 x 14 d 12 x 12 GRAPH A MINIMUM REQUIRED HORIZONTAL DISTANCE BETWEEN A SPRINKLER LO...

Страница 8: ...IS LOCATED AT A PEAK NOTES UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED THE MOUNTING SURFACE MUST BE LOCATED WITHIN 4 TO 6 INCHES OF THE PEAK IF IT IS NOT...

Отзывы: