background image

the Deflector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt to mod-
ify or repair a damaged sprinkler.

Step 7.

When installing an Air and

Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
Dust Seal, verify the angle of the out-
side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
the Retainer in the grooved slot of the
Air and Dust Seal and continue around
the retainer until the entire Air and
Dust Seal is engaged.

NOTE

The Air and Dust Seal is only to be
installed on the periphery of the Re-
tainer.

Step 8.

Screw on the Cover Plate/Re-

tainer  Assembly  until the Retainer -
Figure 2 (or Air and Dust Seal - Figure
5) contacts with the ceiling. Do not
continue to screw on the Cover
Plate/Retainer Assembly such that it
lifts a ceiling panel out of its normal
position. If the Cover  Plate/Retainer
Assembly cannot be engaged with the
Support Cup or the Cover Plate/Re-
tainer Assembly cannot be engaged
sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.

Care and
Maintenance

The Series RFII must be maintained
and serviced in accordance with the
following instructions:

NOTES

Absence of the Cover Plate Assembly
may delay sprinkler operation in a fire
situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This

TFP181

Page 3 of 4

FIGURE 2

SERIES RFII CONCEALED SPRINKLER

INSTALLATION DIMENSIONS

A: 3-1/4" (82,6 mm)

C: 2-3/8" to 2-5/8" (60,3 to 66,7 mm)

B: 3/16" (4,8 mm)

D: 1-3/4" to 2-1/4" (44,5 to 57,2 mm)

COVER PLATE

PROFILE DEPTH

DIMENSION B

1/2" (12,7 mm)

THREADED

ADJUSTMENT

D

SPRINKLER

FACE OF

FITTING

RETAINER

ASSEMBLY

MANUFACTURER

3/32" (2,4 mm)

PRESET GAP

FACE OF CEILING,

RETAINING RING

MOUNTING

SURFACE

SUPPORT CUP

SPRINKLER

ASSEMBLY

DIAMETER

CLEARANCE HOLE

DEFLECTOR

IN DROPPED

POSITION

(4,8 to 17,5 mm)

3/16" to 11/16"

REFERENCE

COVER PLATE

COVER PLATE

DIAMETER

DIMENSION A

DIMENSION C

FIGURE 3

RFII SPRINKLER WRENCH

FRAME

ARM

SUPPORT

CUP

7/8" (23 mm)

SQUARE

1/2" SOCKET

ACCEPTS

DRIVE

ARROWS WITH

ALIGN

FRAME ARMS

FIGURE 4

DISPOSABLE PROTECTIVE CAP

CLEARANCE

HOLE

OBSOLETE