INSTALLATION

NOTE

Do not install any bulb type sprinkler

if the bulb is cracked or there is a loss

of liquid from the bulb. With the

sprinkler held horizontal, a small air

bubble should be present. The diame-

ter of the air bubble is approximately

1/16 inch (1,6 mm) for the

135°F/57°C to 3/32 inch (2,4 mm) for

the 286°F/141°C temperature rat-

ings.

The Model F895 ECOH Sprinklers
must be installed in accordance with
the following instructions.

1. Prior to installing each sprinkler, ver-

ify that the face of the sprinkler fitting
is within the proper range of distance
which can be accommodated by the
particular type of escutcheon.

When installing the F895 Sprinkler
with the F700 Recessed Escutch-
eon, for best overall appearance,
use Dimension “A” indicated under
the  “Fully  Recessed  Dimensions”
heading of Figure B. Otherwise, use
Dimension “A” under the “High Ad-
justment Dimensions” heading. In
either case, the remaining adjust-
ment can then be used to compen-
sate for the possible manufacturing
variations in the take-out of the fit-
tings, as well as in the make-in of the

sprinklers  (as permitted by ANSI
B1.20.1).

2. The sprinkler must be installed with

the deflector parallel to the mounting
surface. Pendent sprinklers must be
installed in the pendent position, and
upright sprinklers must be installed
in the upright position.

3. With pipe thread sealant applied to

the pipe threads and after installing
the F700 Mounting Plate (or other
escutcheon, as applicable) over the
sprinkler threads, hand tighten the
sprinkler into the sprinkler fitting.

4. Wrench tighten upright or pendent

sprinklers using only the W-Type 3
(End A) Sprinkler Wrench. Wrench
tighten the recessed pendent sprin-
kler using only the W-Type 4 Sprin-
kler Wrench. The wrench recess of
the applicable wrench (Ref. Figures
C and D) is to be applied to the
sprinkler wrench flats (Ref. Figure
A).

NOTES

A leak tight 3/4 inch NPT sprin-

kler joint should be obtained with

a torque of 10 to 20 ft.lbs. (13,4 to

26,8 Nm). Higher levels of torque

may distort the sprinkler inlet

—4—

Coverage Area

Ft. x Ft.

Sq. Ft.

Maximum

Distance

From

Wall

Ft.

14 x 14

16 x 16

196

256

7

8

29.6

38.4

11.8

7.0

39.2

51.2

12.3

20.9

Minimum

Flow,
GPM

Minimum

Flow,
GPM

Minimum

Pressure,

PSI

Minimum

Pressure,

PSI

0.15 gpm/ft

2

Density

0.20 gpm/ft

2

Density

K=11.2

ORDINARY HAZARD

GROUP 2

ORDINARY HAZARD

GROUP 1

K=14.0

Coverage Area

Ft. x Ft.

16 x 16

18 x 18

20 x 20

256

324

400

Sq. Ft.

Maximum

Distance

From

Wall

Ft.

8

9

ORDINARY HAZARD

GROUP 1

ORDINARY HAZARD

GROUP 2

0.15 gpm/ft

2

Density

0.20 gpm/ft

2

Density

Minimum

Flow,
GPM

Minimum

Pressure,

PSI

Minimum

Flow,
GPM

Minimum

Pressure,

PSI

38.4

48.6

7.5

12.1

51.2

64.8

13.4

21.4

10

60.0

18.4

80.0

32.7

TABLE B

UL AND C-UL LISTING CRITERIA FOR THE INSTALLATION OF

MODEL F895 ECOH SPRINKLERS

Conversion Factors

1 ft. =

0.03048 m

1 sq. ft. =

0.093 m

2

1 gpm =

3.785 lpm

1 psi =

0.06895 bar

1 gpm/ft

2

= 40.74 mm/min

FIGURE D

W-TYPE 4 SPRINKLER WRENCH

(For Recessed Installations)

RECESS

2

WRENCH

WRENCH

LUGS

1

"FITTING SIDE"

FITTING

TOWARDS SPRINKLER

RECESS

WRENCH

(END "A")

FIGURE C

W-TYPE 3 SPRINKLER WRENCH

(For Pendent & Upright

Installations)

OBSOLETE