Deep Ceiling Escutcheon, hold the
outer piece in contact with the mount-
ing surface (ceiling), and then rotate
the inner piece approximately 1/4 turn
with respect to the outer piece, to hold
the Deep Escutcheon firmly together.

Care and
Maintenance

The Series DS-1 Dry Type Sprinklers
must be maintained and serviced in
accordance with the following instruc-
tions:

NOTES

Absence of the outer piece of an es-
cutcheon, which is  used to cover a
clearance hole, may delay the time to
sprinkler operation in a fire situation.

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties and all personnel who may be
affected by this action must be notified.

A Vent Hole is provided in the Bulb
Seat (Ref. Figure 1) to indicate if the
Dry Sprinkler is remaining dry. Evi-
dence of leakage from the Vent Hole is
an indication that there may be
weepage past the Inlet seal and that
the sprinkler needs to be removed for
determining the cause of leakage (e.g.
an improper installation or an ice plug).
The fire protection system control
valve must be closed and the system
drained before removing the sprinkler.

Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.

Automatic sprinklers must  never be
shipped or stored where their tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified sprinklers must be re-
placed. Sprinklers that have been ex-
posed to corrosive products of com-
bustion, but have not operated, should
be completely cleaned by wiping the
sprinkler with a cloth or by brushing it
with a soft bristle brush.

Care must be exercised to avoid dam-
age - before, during, and after instal-
lation. Sprinklers damaged  by drop-
ping,  striking, wrench twist/slippage,
or the like, must  be replaced. Also,
replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb (Ref. Installation Section).

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-

vices in  compliance with this  docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.

It is recommended that automatic
spr inkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Limited
Warranty

Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty

is

given

for

products

or

components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED   AN   AMOUNT
EQUAL TO THE SALES PRICE.

THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL

OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.

Ordering
Procedure

Contact your local distributor for avail-
ability, and please specify the follow-
ing:

1. Sprinkler.

Model/SIN.

Standard Response, Standard
Coverage, Dry Type Sprinkler

Deflector Style.

5.6 K-factor.

Order Length.

Dry Type Sprinklers are furnished
based upon Order Length as
measured per Figures 3 through
8, as applicable. After the meas-
urement is taken, round it to the
nearest 1/4 inch increment.

Inlet Connection (1 Inch NPT is
standard).

Temperature Rating.

Sprinkler Finish.

Escutcheon Style and Finish, as
applicable.

Part Number from Table B. (Part
numbers are for 1 inch NPT stan-
dar order sprinklers. Orders for all
other sprinkler assemblies must
be accompanied by a complete
description.)

2. W-Type 7 Sprinkler Wrench.

Refer to the Price List for complete
listing of Part Numbers.

TFP500