Storage Type

NFPA

FM Global

Open Frame (i.e., no solid shelves)

Single, Double, Multiple-Row, or Portable Rack Storage of 

Class I-IV and Group A or B Plastics

Refer to NFPA 13 

Chapters 16 and 17

Refer to FM Global 

2-0 and 8-9

Solid Pile or Palletized Storage of 

Class I-IV and Group A or B Plastics

Refer to NFPA 13 

Chapters 14 and 15

Refer to FM Global 

2-0 and 8-9

Idle Pallet Storage

Refer to NFPA 13 

Chapter 12

Refer to FM Global 

2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13 

Chapter 18

Refer to FM Global 

2-0 and 8-3

Roll Paper Storage 

(Refer to the Standard)

Refer to NFPA 13 

Chapter 19

Refer to FM Global 8-21

Flammable/Ignitable Liquid Storage 

(Refer to the Standard)

Refer to NFPA 30

Refer to FM Global 7-29

Aerosol Storage 

(Refer to the Standard)

Refer to NFPA 30B

Refer to FM Global 7-31

Automotive Components in Portable Racks 

(Control mode only; refer to the Standard)

N/A

N/A

N/A – Not Applicable

1" NPT

- Hook

4

-

7
8 -

5
6

-
- Link Assembly

Sealing

Assembly

Button

Strut

-

2
3 -

1 -

Compression

Screw

Deflector

Frame

CENTERLINE

OF THERMAL

SENSING

ELEMENT

WRENCH

FLATS

1-3/4"

(44,5 mm)

DIA.

2

3

3-3/16"

(81,0 mm)

1-5/8"

(41,3 mm)

1-9/16"

(39,9 mm)

4

6

5

7

1

8

FIGURE 1  

MODEL ESFR-22 (TY8226) EARLY SUPPRESSION, FAST RESPONSE 

PENDENT SPRINKLER 22.4 K-FACTOR

TABLE A 

MODEL ESFR-22 PENDENT SPRINKLERS 

 COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

OBSOLETE

Содержание ESFR-22

Страница 1: ...addition to the standards of any authorities having jurisdiction e g FM Global Failure to do so may impair the performance of these devices The owner is responsible for maintaining their fire protection system and devices in proper operating condition Contact the installing contractor or product manufacturer with any questions In all cases the appropriate NFPA or FM installation standard or other ...

Страница 2: ...andard Refer to NFPA 13 Chapter 19 Refer to FM Global 8 21 Flammable Ignitable Liquid Storage Refer to the Standard Refer to NFPA 30 Refer to FM Global 7 29 Aerosol Storage Refer to the Standard Refer to NFPA 30B Refer to FM Global 7 31 Automotive Components in Portable Racks Control mode only refer to the Standard N A N A N A Not Applicable 1 NPT Hook 4 7 8 5 6 Link Assembly Sealing Assembly Butt...

Страница 3: ...g Distance NFPA 6 to 18 inches 152 to 457 mm Centerline of Thermal Sensing Element to Ceiling Distance FM Global See FM Global 2 0 for Storage Sprinklers Operation The fusible link assembly is com prised of two link halves that are joined together by a thin layer of solder When the rated temperature is reached the solder melts and the two link halves separate activating the sprinkler and flowing w...

Страница 4: ... or the like must be replaced The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Asso ciation e g NFPA 25 in addition to the standards of any authorities having jurisdiction Contact the installing con tractor or product manufacturer ...

Отзывы: