Care and
Maintenance

The Series TY-B Sprinklers must be
maintained and  serviced in accord-
ance with the following instructions:

NOTES

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.

Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.

Automatic sprinklers must  never be
shipped or stored where their tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated
or otherwise altered after leaving the
factory. Modified sprinklers must be re-
placed. Sprinklers that have been ex-
posed to corrosive products of com-
bustion, but have not operated, should
be  replaced  if  they cannot  be  com-
pletely cleaned by wiping the sprinkler
with a cloth or by brushing it with a soft
bristle brush.

Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).

Frequent  visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after  the  installation has  been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in  compliance with this  docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-

stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.

It is recommended that automatic
spr inkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Limited
Warranty

Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty

is

given

for

products

or

components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED   AN   AMOUNT
EQUAL TO THE SALES PRICE.

THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.

Ordering
Procedure

When placing an order, indicate the full
product name. Refer to the Price List
for complete listing of Part Numbers.

Contact your local distributor for avail-
ability.

Upright Sprinkler Assemblies with
Shield and NPT Thread
Connections:

Specify: (Specify Model/SIN), Stand-
ard Response, (specify K-factor),
(specify temperature rating), Series
TY-B Upright Intermediate Level Sprin-
kler with (specify type of finish or coat-
ing), P/N (specify from Table B).

Pendent Sprinkler Assemblies with
(Shield Ordered Separately) and
NPT Thread Connections:

Specify: (Specify Model/SIN), Stand-
ard Response, (specify K-factor),
(specify temperature rating), Series
TY-B Pendent Sprinkler with (specify
type of finish or coating), P/N (specify
from Table C)

Model S2 Pendent Shield & O-Ring:

Specify: S2 Pendent Shield & O-Ring
for use with (specify 1/2" NPT or 3/4"
NPT) Series TY-B Pendent Sprinklers,
P/N (specify).

1/2" NPT S2

Pendent Shield
& O-Ring . . . . . . . . . . . . . . P/N 56-070-9-332

3/4" NPT S2

Pendent Shield
& O-Ring . . . . . . . . . . . . . . P/N 56-070-9-342

Sprinkler Wrench:

Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.

Wax Sticks:
(for retouching wrench damaged
wax coating)

Specify: (Specify color) color coded
Wax Stick for retouching (specify tem-
perature rating) temperature rated Se-
ries TY-B Sprinklers, P/N (specify).

Black for 135°F . . . . . . . . . . . . P/N 56-065-1-135
Red for 155°F . . . . . . . . . . . . . P/N 56-065-1-155
Yellow for 175°F

. . . . . . . . .

P/N 56-065-1-175

Blue for 200°F and

286°F . . . . . . . . . . . . . . . . . P/N 56-065-1-286

NOTES

Each wax stick is suitable for retouch-
ing up to twenty-five sprinklers.

The wax used for 286°F sprinklers is
the same as for 200°F sprinklers, and,
therefore, the 286°F sprinkler is limited
to the same maximum ceiling tempera-
ture as the 200°F sprinkler (i.e.,
150°F).

TFP351

Page 5 of 6

OBSOLETE

Содержание CENTRAL TY-B Series

Страница 1: ...tion of chemicals and gas chemical velocity should be con sidered as a minimum along with the corrosive nature of the chemical to which the sprinklers will be exposed WARNINGS The Series TY B Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the standar...

Страница 2: ...IES TY B UPRIGHT TY4153 AND PENDENT TY4251 SPRINKLERS INTERMEDIATE LEVEL SPRINKLERS 8 0 K FACTOR 3 4 INCH NPT SCREW SHIELD UPRIGHT SHIELD MODEL S2 SHIELD FIELD ASSEMBLED SEE INSTALLATION SECTION 2 3 16 55 6 mm PENDENT WRENCHING FLATS NOMINAL MAKE IN 7 16 11 1 mm 1 2 NPT O RING 60 3 mm FACTORY ASSEMBLED UPRIGHT 1 2 NPT 11 1 mm MAKE IN NOMINAL 7 16 2 3 8 3 1 2 88 9 mm DIA FLATS WRENCHING 3 1 2 88 9 ...

Страница 3: ...d Coated Wax Coated and Wax over Lead Coated Sprinklers are noted to be FM Approved the sprinklers are FM Approved as Corrosion Resistant Sprinklers 150 F 66 C Maximum Ceiling Temperature With Zinc Plated Shield N A Not Available TABLE A LABORATORY LISTINGS AND APPROVALS WAX OVER LEAD COATED LEAD COATED WAX COATED 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 N A K 5 6 1 2 NPT PENDENT TY3251 135 F 57 C ...

Страница 4: ...ield past the threads Step 2 Roll the O Ring over the sprin kler threads until it seats against the Shield Step 3 With pipe thread sealant ap plied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 4 Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench Ref Figure 3 With reference to Figure 1 or 2 the W Type 6 Sprinkler Wrench is to ...

Страница 5: ...hip with Tyco Fire Products or for products and components which have been subject to misuse improper installation corro sion or which have not been installed maintained modified or repaired in ac cordance with applicable Standards of the National Fire Protection Associa tion and or the standards of any other Authorities Having Jurisdiction Mate rials found by Tyco Fire Products to be defective sh...

Страница 6: ...41 C MAX 8 WAX OVER LEAD 286 F 141 C MAX 543 8 0K UPRIGHT 3 4 NPT 533 5 6K UPRIGHT 1 2 NPT TY3153 TY4153 P N 57 XXX X XXX 360 F 182 C 155 F 68 C 360 155 TEMPERATURE RATING 135 F 57 C 135 1 SPRINKLER TABLE C PART NUMBER SELECTION SERIES TY B PENDENT SPRINKLERS MODEL S2 PENDENT SHIELD O RING MUST BE SEPARATELY ORDERED 175 F 79 C 286 200 F 93 C 200 286 F 141 C 175 NATURAL BRASS 9 MODEL SIN CHROME PLA...

Отзывы: