Tyco Fire Product CENTRAL Omega HEC-12 PRO Prohibitor Скачать руководство пользователя страница 2

2

Rigid Support Collar

Omega HEC Sprinkler Wrench

Tamper-proof Socket

Note:  A special tamper-proof socket must be used for installation or removal of the tamper-resistant retaining screws.

Installation Diagram - HEC-12 PRO

Finished Ceiling

Finished Wall

Closure Plate (Optional)

Ridgid Support Collar With Hex 
Bolt (To prevent movement of
          sprinkler head away from
          finished wall surface)

Retaining Collar

Branch 

Line Fitting

1" N.P.T. Steel Nipple

1" x 1/2" N.P.T. Reducer

Escutcheon

Tamper-Resistant Screw

2 1/4" Dia. Hole In Wall

 

2 1/2" Escutcheon

3 5/8" Dia. (Escutcheon Closure Plate)

1/2"

1 7/16" 

±

 1/16" No Closure Plate

1 3/8" 

±

 1/16" Escutcheon Closure Plate

1 5/16" 

±

 1/16" Security Closure Plate

4 1/2" Dia. (Security Closure Plate)

1/4" 

±

 1/16"

3/4"

3/8"

2 3/4"

* Shown for reference only, not a height restriction.

4" to 12"

14'-0" (throw)

Centerline of Room

*8'-0"

7'-0"

     7'-0"

(1/2 width)

One(1) Head 15 GPM @   7 PSI
One(1) Head 22 GPM @ 15 PSI
One(1) Head 31 GPM @ 30 PSI

Nominal Wetting Patterns for 14' x 14' Room

HEC-12 PRO
Horizontal
Sidewall Sprinkler

Farwall

Backwall

OBSOLETE

Содержание CENTRAL Omega HEC-12 PRO Prohibitor

Страница 1: ...is movement allows system water pressure to force the orifice sealing mechanism and deflector assembly open Water is then discharged in a designed flow pattern The Omega ProhibitorTM Model HEC 12 PRO Automatic Sprinklers have been specifically designed for use in institutional occupancies such as correctional facilities and mental health facilities where the occupants may attempt to tamper with or...

Страница 2: ...ng 1 N P T Steel Nipple 1 x 1 2 N P T Reducer Escutcheon Tamper Resistant Screw 2 1 4 Dia Hole In Wall 2 1 2 Escutcheon 3 5 8 Dia Escutcheon Closure Plate 1 2 1 7 16 1 16 No Closure Plate 1 3 8 1 16 Escutcheon Closure Plate 1 5 16 1 16 Security Closure Plate 4 1 2 Dia Security Closure Plate 1 4 1 16 3 4 3 8 2 3 4 Shown for reference only not a height restriction 4 to 12 14 0 throw Centerline of Ro...

Страница 3: ...he male threads only Step 4 Hand tighten the sprinkler into the reducing coupling Use an Omega HEC sprinkler wrench to tighten the unit into the fitting A leak tight joint requires the application of only 7 to 14 ft lbs of torque A tangential force of 14 to 28 lbs delivered through a 6 long handle will deliver adequate torque Torque levels over 21 ft lbs may distort the orifice seal resulting in l...

Страница 4: ...tivity Do not attempt to re assemble or otherwise reuse a sprinkler that has operated Replace any sprinkler exhibiting corrosion or damage always use new sprinklers of the same type and temperature rating as replacements Because the discharge pattern is critical to protection of life and property nothing should be hung or attached to the sprinkler unit that would disrupt the discharge pattern Such...