background image

Temperature Rating: 155

°

F/68

°

C

200

°

F/93

°

C

286

°

F/141

°

C

Hydraulic Design Criteria:   The density required is

0.60 gpm/sq. ft. (24,5 mm/min).

Design Area:

For wet systems 2000 sq. ft. (186 m

2

)

and for dry systems use 2600 sq. ft.
(242 m

2

)

Spacing:

Maximum spacing is 100 sq. ft.
(9,3 m

2

).  The maximum distance

between sprinklers is 12'-0" (3,7 m) -
12'-6"(3,8 m) spacing is allowed in
25'-0"(7,6 m) bays.  Minimum spacing
is 6'-0" (1,8 m) apart unless
separated by baffles.

Obstructions:

NFPA criteria for standard spray
sprinklers.

Type of Storage:  Single, double, multiple-row and

portable rack storage (No Solid
Shelves) and solid piled or
palletizied storage.

Commodity:  Class I-IV, encapsulated or non-

encapsulated.  Group A and B plastics -
cartoned, expanded or unexpanded as
well as exposed, unexpanded.

Maximum Storage Height: 20'-0" (6,1 m)

Clearance:

36" (0,9 m) minimum from deflector
to top of storage.

Max. Ceiling Height in Area of Storage: 25'-0" (7,6 m)

Construction Type:  All types - deflector distances per
                                   NFPA 13.

System Type:      Wet or dry

Table 2 - K17-231, UL & C-UL Specific Application Guidelines

Figure 3 - Cross Section

Model K17-231, Upright Sprinkler

Figure 4 - W-Type 8, Sprinkler Wrench (Part #1068)

SPRINKLER

FRAME

DEFLECTOR

GLASS BULB

OPERATING 

ELEMENT

GASKETED 

SPRING PLATE

(BELLEVILLE 

SEAL)

BUTTON 

ASSEMBLY

COMPRESSION

SCREW

WRENCH

RECESS