background image

2

Figure 2

Model GB& GB-QR Dry Sidewall Extended

Figure 1

Model GB & GB-QR Dry Sidewall

Flush & Recessed

Figure 3

Model GB& GB-QR Dry Sidewall Slatted Walls

Caution:  See step one of installation sequence for appropriate fitting requirements.

Ordering Length for Dry Pendent Heads

Flush 

— The “A” dimension is measured from the face of the tee to the finished wall.  This is only approximately flush.  Order to the nearest 

1

4

"

(6.4 mm).   Minimum “A” dimension is 2" (50.8 mm).

Slatted 

— The “A” dimension is measured from the face of the branchline tee to the face of the finished slatted wall.  Minimum “A” dimension is

1

1

2

" (38.1 mm).  The adjustment is +

1

2

" (12.7 mm).

Recessed

 — The “A” dimension is measured from the face of the tee to the finished wall.  Minimum “A” dimension is 2

1

8

" (54.0 mm).  Adjust-

ment is 

±

 3

16

" (4.8 mm).

Extended

 — The “A” dimension is measured from the face of the tee to the finished wall.  Follow one of these two options:

If the “A” dimension is less than or equal to 3

1

4

" (82.6 mm), total adjustment is 1

1

2

" (38.1 mm) (from the mid point of the adjustment range 

±

3

4

"

(19.1 mm)).  Order to the nearest 

1

4

" (6.4 mm).  Minimum “A” dimension is 0".

If the “A” dimension is greater than 3

1

4

" (82.6 mm), the total adjustment is 3" (76.2 mm) (from the mid point of the adjustment range 

±

1

1

2

" (38.1 mm)).

Order to the nearest 

1

4

" (6.4 mm).  Minimum “A” dimension is 3

1

4

" (82.6 mm).

K-Factor Table

Length

K-Factor (metric)

2

1

2

" (63.5 mm) to less than 10

1

8

" (254.1 mm)

5.3 (76.4)

10

1

8

" (254.1 mm) to less than 17

5

8

" (447.7 mm)

5.2 (75.0)

17

5

8

" (447.7 mm) to less than 25

1

4

" (641.4 mm)

5.1 (73.5)

25

1

4

" (641.4 mm) to less than 32

3

4

" (831.9 mm)

5.0 (72.1)

32

3

4

" (831.9 mm) to less than 40

3

8

" (1025.5 mm)

4.9 (70.7)

40

3

8

" (1025.5 mm) to less than 48" (1219.2 mm)

4.8 (69.2)

Dry Pendent Design Guidelines

To determine the K-factor, follow these steps:

1.  Determine the K-factor length (NOT The “A” DIMENSION).  The

K-factor is determined as follows:

Slatted - “A”  dim1

3

8

" (34.9 mm) = length for K-factor.

Flush - “A” dim

7

8

" (22.2 mm) = length for K-factor.

Recessed - “A” dim

3

8

" (9.5 mm) = length for K-factor.

Extended - “A” dim3

1

2

" (88.9 mm) = length for K-factor.

2.  Determine the K-factor for that length by using the K-factor table.
3.  Use the K-Factor at the tee in the branchline for your calculations.

1" (25 mm)

Thread

“A”

Dimension

(order length)

Main
Tube

Finished Wall

LIne

2 1/2" (63.5 mm)

±

1/8" (3.8 mm)

Ceiling Opening

1 15/16" (49.2 mm)

Inner Cup Dia.

If A is > 3 1/4" (82.6 mm)

Dimension is 4 5/8" (117.5 mm)

(

±

1 1/2" (38.1 mm))

If A is 

 3 1/4" (82.6 mm)

Dimension is 3 7/8" (98.4 mm)

(

±

3/4" (19.1 mm))

Finished Wall

LIne

1" (25 mm)

Thread

Main Tube

“A”

Dimension

(order length)

2 1/2" (63.5 mm)

±

1/8" (3.8 mm)

Ceiling Opening

1 15/16"

(49.2 mm)

Inner Cup Dia.

Flush

1 7/8" (47.6 mm)

Recessed

1 1/2" (38.1 mm)

Finished Wall

LIne

1" (25 mm)

Thread

Main Tube

“A”

Dimension

(order length)

2 1/2" (63.5 mm)

±

1/8" (3.8 mm)

Ceiling Opening

1 15/16"

(49.2 mm)

Inner Cup Dia.

2 1/2" (

±

1/2")