Design
Data

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Density 0.15 GPM/ft

2

 - NFPA 13 1991 and later

Temperature Rating 155

°

F/68

°

C, 200

°

F/93

°

C and 250

°

F/121

°

C

Caution:  Minimum spacing between upright sprinklers is 14' 

(4.3m)

.

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Density 0.21 GPM/ft

2

 - NFPA 13 1989 or earlier

Temperature Rating 155

°

F/68

°

C, 200

°

F/93

°

C and 250

°

F/121

°

C

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Density 0.20 GPM/ft

2

 - NFPA 13 1991 and later

Temperature Rating 155

°

F/68

°

C, 200

°

F/93

°

C and 250

°

F/121

°

C

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Density 0.19 GPM/ft

2

 - NFPA 13 1989 or earlier

Temperature Rating 155

°

F/68

°

C, 200

°

F/93

°

C and 250

°

F/121

°

C

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Density 0.16 GPM/ft

2

 - NFPA 13 1989 or earlier

Temperature Rating 155

°

F/68

°

C, 200

°

F/93

°

C and 250

°

F/121

°

C

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

psi

(bar)

18 x 18 feet (324 sq. ft.)

  9 feet

48.6

11.2

5.5 x 5.5 m(30.1m

2

)

(2.7m)

(184.2)

(0.8 )

20 x 20 feet (400 sq. ft.)

10 feet

60.0

17.1

6.1 x 6.1 m(37.2m

2

)

(3.0m)

(227.4)

(1.2)

Installation

All Central Model ESLO-20 GB

Upright Automatic Glass Bulb Sprin-
klers must be installed according to
current NFPA 13 Standards and
these installation instructions.  Devia-
tions from these requirements and
standards or any alteration to the
sprinkler itself will void any warranty
made by Central Sprinkler Company.
In addition, installation must also
meet local government provisions,
codes, and standards as applicable.

The system piping must be properly

sized to ensure the minimum required
flow rate at the sprinkler.  Check for
the proper model, style, orifice size,
and temperature rating prior to
installation.  Install sprinklers after the
piping is in place to avoid mechanical
damage; replace any damaged units.

 Wet pipe systems must be

protected from freezing.

Upon completion of the installation,

the system must be tested per
recognized standards.

In the event of a thread leak,

remove the unit, apply new pipe joint
compound or tape, and reinstall.

Installation Sequence

Step 1.  The sprinkler must be
installed in the upright position.

Step 2.  Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply only to the male threads.

Step 3.  Hand tighten the sprinkler
into the fitting.  Use a Central
Sprinkler Wrench, to tighten the unit
into the fitting.  A leak-tight joint
requires only 7 to 14 ft.-lbs.

(9.5 to 19.0

Nm)

 of torque; a tangential force of 14

to 28 lbs.

(62.3 to 124.5 N)

 delivered

through a 6"

(150 mm)

 handle will

deliver adequate torque.  Torque
levels over 21 ft.-lbs.

(28.6 Nm)

 may

distort the orifice seal, resulting in
leakage.

The sprinkler shall be oriented so

the frame arms are parallel with the
branch line pipe for upright sprinklers.

*Teflon is a trademark of the DuPont Corp.

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

psi

(bar)

18 x 18 feet (324 sq. ft.)

  9 feet

51.8

12.8

5.5 x 5.5 m(30.1m

2

)

(2.7m)

(196.3)

(0.9)

20 x 20 feet (400 sq. ft.)

10 feet

64.0

19.5

6.1 x 6.1 m(37.2m

2

)

(3.0m)

(242.6)

(1.3)

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

psi

(bar)

18 x 18 feet (324 sq. ft.)

  9 feet

61.6

18.0

5.5 x 5.5 m(30.1m

2

)

(2.7m)

(233.5)

(0.8)

20 x 20 feet (400 sq. ft.)

10 feet

76.0

27.5

6.1 x 6.1 m(37.2m

2

)

(3.0m)

(288.0)

(1.9)

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

psi

(bar)

18 x 18 feet (324 sq. ft.)

  9 feet

64.8

20.0

5.5 x 5.5 m(30.1m

2

)

(2.7m)

(245.6)

(1.4)

20 x 20 feet (400 sq. ft.)

10 feet

80.0

30.4

6.1 x 6.1 m(37.2m

2

)

(3.0m)

(303.2)

(2.1)

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

psi

(bar)

18 x 18 feet (324 sq. ft.)

  9 feet

68.0

22.0

5.5 x 5.5 m(30.1m

2

)

(2.7m)

(257.7)

(1.5)

20 x 20 feet (400 sq. ft.)

10 feet

84.0

33.6

6.1 x 6.1 m(37.2m

2

)

(3.0m)

(318.4)

(2.3)