General
Description

The Model ESFR-17 Sprinklers (Ref.
Figure 1) are “Early Suppression
Fast Response Sprinklers” having a
nominal K-factor of 16.8. They are
suppression mode sprinklers, and
their use is especially advantageous
as a means of eliminating the use of
in-rack sprinklers, when protecting
high-piled storage.

The Model ESFR-17 is primarily de-
signed for use in ceiling only sprin-
kler systems (i.e. no in-rack sprin-
klers) for the protection of storage
heights of most encapsulated or non-
encapsulated common materials in-
cluding cartoned unexpanded plas-
tics of up to 35 ft. (10,7 m) and with
ceiling heights of up to 40 ft. (12,2
m), as well as cartoned expanded
plastics of up to 25 ft. (7,6 m) with
ceiling heights of up to 30 ft.(9,1 m).
In addition, the protection of some
storage arrangements of roll paper
and rubber tires can be considered
as well.

Also, in some cases, the Model
ESFR-17 can be used to protect stor-
age heights up to 40 ft. (12,2 m) with
ceiling heights up to 45 ft. (13,7 m)
in combination with one level of in-
rack sprinklers.

The ESFR-17 provides the system
designer with hydraulic options not
presently available to the traditional
ESFR sprinklers having a nominal
K-Factor of 14.0. In particular, the
Model ESFR-17 has been designed
to operate at substantially lower end
head pressures, as compared to
ESFR sprinklers having a nominal
K-Factor of 14.0. This feature offers
flexibility when sizing the system pip-
ing, as well as possibly reducing or
eliminating the need for a system fire
pump.

Operation.

The fusible link assembly

is comprised of two link halves which
are joined together by a thin layer of
solder. When the rated temperature
is reached, the solder melts and the
two link halves separate, which then
allows the sprinkler to activate and
flow water.

WARNINGS

The Model ESFR-17 Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any other authori-
ties having jurisdiction (e.g., FM
Global). Failure to do so may impair
the integrity of these devices.

The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. The installing contractor or
sprinkler manufacturer should be
contacted relative to any questions.

Technical
Data

Sprinkler Identification Number

SIN TY7226

Approvals

FM Approved under the name of
Tyco Fire Products.
(Refer to the Design Criteria Section)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

3/4 inch NPT or ISO 7-R3/4

Discharge Coefficient

K = 16.8 GPM/psi

1/2

(241,9 LPM/bar

1/2

)

Temperature Ratings

165°F/74°C or 214°F/101°C

Finish

Natural Brass

Physical Characteristics

The Model ESFR-17 utilizes a dezin-
cification resistant bronze alloy
frame. The strut and hook are monel;
and, the button, deflector, and com-
pression screw are bronze. The
frame orifice is sealed with a gas-
keted spring plate (Belleville Seal)
consisting of a beryllium nickel disc
spring that is sealed on both its in-
side and outside edges with a Tef-
lon

†

gasket, and the two halves of

the fusible link assembly are nickel.

Early
Suppression
Fast Response
Pendent
Sprinklers

No. 3-1.5

D

upont

Registered

T

ra

demar

k

Model ESFR-17

Early Suppression
Fast Response Sprinklers

Tyco Fire Products — www.centralsprinkler.com