background image

3/4" NPT

3-1/8" (79,4 mm)

ELEVATION VIEW

TOP OF SPRINKLER

DEFLECTOR

7/16"

(11,1 mm)

CENTRAL

SPRINKLER

FRAME

DEFLECTOR

GLASS BULB

OPERATING ELEMENT

GASKETED SPRING PLATE

(BELLEVILLE SEAL)

BUTTON 

ASSEMBLY

COMPRESSION

SCREW

Design
Criteria

The Model ELO SW-20 ECOH Horizontal Sidewall Sprinklers are UL and C-UL listed and NYC Approved (MEA 466-92-E
Vol. 7), for use in ordinary hazard occupancies with non-combustible unobstructed construction, using the design criteria in
Table 1 as well as any additional requirements specified in current NFPA 13 Standards for Extended Coverage Sidewall
Sprinklers.

These sprinklers are listed with a ceiling to top of sprinkler deflector distance of 6 - 12 inches (152,4 - 304,8 mm).

A 36 inch (914,4 mm) clearance must be maintained between the top of the sprinkler deflector and any miscellaneous
storage.

The Horizontal Sidewall Sprinklers must be installed in such a manner, that no other sprinkler is located within the maximum
protection area of any other sprinkler.

These sprinklers may be installed on sloped ceilings in loading docks, with a maximum roof slope of 4 inches per foot as
indicated in Figure 3 of this data sheet.

The Model ELO SW-20 ECOH Horizontal Sidewall Sprinklers may be used with any metalic flush or extended escutcheon,
provided the maximum ceiling and/or wall to top of sprinkler deflector dimension specified in this document and NFPA 13 is
maintained.  These sprinklers are not listed for recessed applications.

Maxim

um Thro

w

6" to 12"

Ceiling to top of 

Sprinkler Deflector 

Distance

16.4  Max.

o

Figure 2 - Cross Section Model ELO SW-20,

Horizontal Sidewall Sprinkler

Figure 1 - Model ELO SW-20,

Horizontal Sidewall Sprinkler

Figure 3 - Sprinkler Placement on Sloped Ceilings

in loading docks

Figure 4 - W-Type 3, Sprinkler Wrench

(Part #1073)

OBSOLETE