background image

The Series DS-2 Dry Type Sprinkler is
to be installed in the 1 inch NPT outlet
or run of malleable or ductile iron
threaded tee fittings that meet the di-
mensional requirements of ANSI
B16.3 or cast iron threaded tee fittings
that meet the dimensional require-
ments of ANSI B16.4 with the end
sprinkler fitting on a branch line to be
plugged as shown in Figure 3, 4, or 5.

When

installing 1 inch NPT Series

DS-2 Dry Type Sprinklers on a dry pipe
sprinkler system, only use the side out-
let of maximum 2-1/2 inch size reduc-
ing tee’s.

For wet pipe sprinkler systems, the
Series DS-2 Dry Type Sprinklers may
also be installed in the 1 inch NPT

TFP530

Page 3 of 6

FIGURE 2

TY5255 STANDARD RESPONSE or TY5235 QUICK RESPONSE

SERIES DS-2 DRY PENDENT w/ FLUSH ESCUTCHEON

9/16"

(14,3 mm)

NOMINAL

MAKE-IN:

1" NPT

(REFER TO DESIGN

SPRINKLER FITTING

FACE OF

FITTING

SPRINKLER

CRITERIA SECTION)

FACE OF

CEILING

2-1/4±1/8"

(57,2±3,2 mm)

(69,9 mm)

2-3/4" DIA.

(92,1 mm)

3-5/8" DIA.

ADJUSTMENT

WILL PERMIT

ESCUTCHEON

±1/4" (6,4 mm)

ORDER LENGTHS:

INCREMENTS

IN 1/4" (6,4 mm)

(50,8 to 1219,2 mm)

2" to 48"

*

*

1" NPT

MAKE-IN:

NOMINAL

(14,3 mm)

9/16"

FITTING

CEILING

FACE OF

CRITERIA SECTION)

SPRINKLER

FACE OF

SPRINKLER FITTING

(REFER TO DESIGN

(41,3±3,2 mm)

1-5/8±1/8"

2-3/4" DIA.

(69,9 mm)

3-5/8" DIA.

(92,1 mm)

ADJUSTMENT

WILL PERMIT

ESCUTCHEON

±3/8" (9,5 mm)

ORDER LENGTHS:

INCREMENTS

IN 1/4" (6,4 mm)

(69,9 to 1219,2 mm)

2-3/4" to 48"

*

*

FIGURE 3

TY5255 STANDARD RESPONSE or TY5235 QUICK RESPONSE

SERIES DS-2 DRY PENDENT w/ RECESSED ESCUTCHEON

TABLE B

DISCHARGE COEFFICIENTS

K-FACTOR

LENGTH,

Inches (mm)

2-1/2 to 6-1/4

(63 mm to 159 mm)

6-1/2 to 10-1/2

(165 mm to 266,7 mm)

15 to 18-3/4

(381 mm to 476 mm)

10-3/4 to 14-3/4

(273 mm to 375 mm)

31-1/2 to 35-1/4

(800 mm to 895 mm)

27-1/4 to 31-1/4

(692 mm to 794 mm)

23-1/4 to 26-3/4

(591 mm to 679 mm)

19 to 23

(483 mm to 584 mm)

35-1/2 to 39-1/2

(902 mm to 1003 mm)

39-3/4 to 43-1/2

(1010 mm to 1105 mm)

43-3/4 to 48

(1111 mm to 1219 mm)

K-FACTOR,

GPM/psi

1/2

(LPM/bar

1/2

)

11.2

(161,3)

11.1

(159,8)

11.0

(158,4)

10.9

(157,0)

10.8

(155,5)

10.7

(154,1)

10.6

(152,6)

10.5

(151,2)

10.4

(149,8)

10.3

(148,3)

10.2

(146,9)

Note:

K-Factor Length is determined

as follows:

Flush:

“Order Length” (Fig. 2) plus

1/2 inch (12,7 mm).

Recessed:

“Order Length” (Fig. 3) plus

1/4 inch (6,3 mm).

Extended:

“Order Length” (Fig. 4) plus

3-1/4 inch (82,6 mm).

OBSOLETE