SOLARLOK Interconnection System Installation Manual
Страница 1: ...SOLARLOK Interconnection System Installation Manual...
Страница 2: ...l PN 1718077 1 Do not disconnect under load To protect against shock ensure that conductors and their associated connectors are separated from opposite polarity components Unconnected connectors must...
Страница 3: ...ripping tool strip the wire 9 mm 1 mm without damaging the strands 3 2 Insert the stripped wire into the terminal wire crimp barrel until it stops While holding the wire in place squeeze the crimp too...
Страница 4: ...3 6 Tighten the cable screw lock The initial assembly tightening torque is 1 3 0 2 Nm For this a slotted socket wrench with wrench size 13 mm is recommended 4 Connector Mating When mating the SOLARLO...
Страница 5: ...ssued 8 2010 Installation Manual tycoelectronics com solar All specifications subject to change Consult Tyco Electronics for latest specifications 4 5 Wiring Radius r min 5x cable 6 Connector Unmating...
Страница 6: ...0 mm 0 177 0 236 in 4 1394462 9 Minus Female 4 0mm2 12AWG 4 5 to 6 0 mm 0 177 0 236 in 6 1394462 4 Minus Female 6 0mm2 10AWG 4 5 to 6 0 mm 0 177 0 236 in Male Cable Connectors 1394461 7 Plus Male 2 5m...