Medium Voltage ZnO Surge Arresters

 

2005-06-Arrester installation instr-CIS-Rev 1 

 

1

 

Safety Warning 

Surge  arresters  should  be  installed  only 

by  competent  personnel  familiar  with 

good safety practices and the handling of 

high voltage electrical equipment. 

The  enclosed  installation  instruction  is  not 

intended  as  a substitute for adequate training and 

experience  in  safe  procedures  nor  to  replace  or 

supersede 

existing 

safety, 

operating  and 

maintenance procedures. 

Installation Note 

Arresters  are  typically  to  be  installed  between  the  line 

conductor and ground. 

 

Only  in  a  few  special  cases  (motor  protection,  cable 

sheath  protection,  ...)  arresters  may  be  installed  in  a 

different way. Please consult your system administrator 

for details if required. 

Before Starting 

  Check if all parts (surge arrester & accessories) 

are  included  in  the  box  according  to  the 

description printed on the carton label. 

  If  the  accessories  come  disassembled  please 

assemble  all  parts  as  appropriate  prior  to  the 

final  installation.  Please  refer  to  the  enclosed 

drawings for the correct torque.

 

 

  Check  if  the  arrester  or  the  accessories  have 

been  damaged  during  transport.  Never  install a 

damaged  arrester.  It  may  fail  violently,  causing 

severe personal injury. 

  All  surge  arresters  carry  a  nameplate  giving 

details of arrester type and voltage rating. Check 

the voltage rating of each single arrester. Do not 

install  arresters  with  voltage  ratings  other  than 

specified by your system administrator. 

  Check  if  the  arrester  and  the  accessories  fulfill 

the  local  requirements  in  terms  of  mechanical 

dimensions. Do not alter the arrangement of the 

accessories or the accessory itself! 

Do not leave out any parts! 

  Please ask your local system administrator about 

the  minimum  clearances  you  have  to  meet 

between  live  parts  and  ground.  The  values  for 

outdoor substations do apply. If not available you 

may refer to Table 1 instead showing the values 

according to IEC 60071-2. 

 

If  you  are  installing  a  special  kind  of  surge 

arresters  like  SPA-I  with  insulated  line  lead, 

shorter clearances may apply. Please refer to the 

relevant addendum covering those arresters. 

 

If  unsure  about  assembly  sequence,  please 

request and refer to relevant assembly drawing.  

 

Arresters  applied  at  voltages  higher  than 

rating  may  cause  damage  and  injury. 

Check  the  arrester  rating,  marked  clearly 

on  the  name  plate,  to  ensure  correct 

application! 

Installation 

 

Do  not  handle  the  polymeric  housing  of  the 

arrester with tools! 

 

Certain  type  of  arresters  ave  a  protrusion  at both 

ends of the arrester. 

You  can  hold  the  arrester  there  safetly  with  a 

second  wrench  to  fasten  the  nuts  included  with 

some  accessories. Use the protrusion on the side 

close to the nut to be fastened. 

 

 

In case the arrester hasn’t got a protrusion please 

support the arrester by hand. 

 

  Make sure that the electrical system is de-

energized and earthed. 

!

 

 

!

 