Appendix A – AFC200 frequency converter parameters table
Parameter /
Name
Function
Available options / measurement
unit / comments
Factory
setting
Change
during
opera-
tion
2.112
Emergency
Stop
Emergency stop
from digital in-
puts
0-Off:
the emergency stop function
from digital inputs is disabled
1-DI1 .. 6-DI6:
emergency stop, when
voltage is applied to digital input 1 ...
6
0
NO
GROUP 3: FAILURES
3.02
i
2
t blockade
Switching on
blocking
from thermal
overload
0-NO:
disabled
1-YES:
enabled
0
NO
3.03
I therm.
Setting of elec-
tric motor
thermal protec-
tion current
0.0 ... 200.0 %
100.0 %
NO
3.04 I therm.
0
Setting of ther-
morelay for
stopped drive
0.0 ... 200.0 %
50.0 %
NO
3.05
Therm. Const.
Constant of elec-
tric motor heat-
ing
0 ... 320 min.
3 min
NO
3.10
Ext. fail.
Choice of ex-
ternal failure
source
0-Off:
disabled
1-DI1 .. 6-DI6:
reporting external fail-
ure, when there is voltage supplied on
digital input DI1..DI6
0
YES
3.23
Re.4mA lack
Response to
lack of analog
signal (level <2V
(4mA))
0-No:
no response
1-Warn.:
a warning will be displayed,
device will keep working with last ref-
erenced frequency
2-Fail.:
the device will stop and the in-
dication of failure will be displayed
Note: the system has a deadband
from 2.0V and 4..2mA
0
YES
3.60
Re. RS lack
Response to
lack of commu-
nication through
RS link
0-No:
no response
1-Failure:
the device will stop and the
indicator of failure will be displayed
0
YES
3.61
Rs lack time
Acceptable time
of lack of
communication
through RS link
1 ... 600 s
30 s
YES