Owner's Operation & Safety Manual

SERIES 300V

115 and 230 VOLT AC

FUEL TRANSFER PUMP

Models FR300V, FR301V, FR310V &

FR311V

SAFETY INSTRUCTIONS

To ensure safe and efficient operation, it is essential to read
and follow each of these warnings and precautions.
1. Improper use or installation of this product can cause serious

bodily injury or death.

2. Do NOT smoke near pump or use pump near an open flame

when pumping flammable fluids. Fire could result.

3. A Fill-Rite filter should be used on pump outlet to ensure that no

foreign material is transferred to fuel tank.

4. Use gasoline and oil resistant thread sealant or sealant tape on

all threaded joints to protect against leakage.

5. Storage tank should be anchored to prevent tipping in both the

full and empty conditions.

6. To minimize static electricity buildup, only use static wire,

conductive hose when pumping flammable fluids and keep
nozzle in contact with container being filled.

7. The pump motor is equipped with thermal overload protection. If

overheated, it will shut off without any damage to the windings.
Be sure to turn off the pump power if this occurs. When the
motor cools, it will restart without warning if power is on.

8. Take motors needing service to an authorized repair shop to

maintain “explosion proof” and “rain proof” integrity.

WARNING

This product should not be used for fluid transfer into aircraft.  This
product is not suited for use with fluids for human consumption or
fluids containing water.

DANGER

Electrical wiring should be done by a licensed electrician in
compliance with local, state and national electric code NEC/ANSI/
NFPA 70, NFPA 30, NFPA 30A, as appropriate to the intended use
of the pump. Threaded rigid conduit, seal fittings and conductor seal
should be used. Pump should be properly grounded. Improper use
or installation of this product can cause serious bodily injury or
death.

INSTALLATION

GENERAL

Pumps are furnished with a tank adapter for skid tank mounting;
pedestals are available for island installations. All tanks must be
properly vented. A pressure retaining vent/fill cap can be used to
reduce fuel loss due to evaporation but will reduce flow rate.
Fill-Rite filters are recommended when pumping fuels.
Pump has a built-in check valve with pressure relief to prevent fluid
thermal expansion from causing unsafe system pressures. 

Do not

use additional check valves or foot valves unless they have
a proper pressure relief valve built into them. 

 Additional

check valves will reduce flow rate.
Use a gasoline and oil resistant pipe sealant on all pipe threads to
protect against leaks.

SKID TANK MOUNTING

1. Cut a 1-1/4" pipe that will extend to at least 3" above bottom of

tank when screwed into tank adapter and tank adapter is
screwed into tank flange.

2. Screw pipe into tank adapter, then screw tank adapter into tank

flange.

3. Mount pump on tank adapter.

OPERATING INSTRUCTIONS

1. Reset meter to 0 (if applicable).
2. Remove nozzle from nozzle boot and move switch lever up. This

will turn the pump on.

3. Insert nozzle into container to be filled. To minimize static

electricity buildup, keep nozzle in contact with container.

4. Operate nozzle lever to dispense fluid.
5. When desired amount of fluid has been dispensed, release

nozzle lever, remove nozzle from container, move switch lever
to down position to turn off pump, replace nozzle in boot.

DIRECT MOUNTING TO UNDERGROUND TANK

1. Cut and thread both ends of a 2" pipe that will extend about 31"

above the ground when installed in tank flange.

2. Install this pipe in tank flange. Screw 2" standard pipe coupling

onto top of pipe.

3. Cut a 1-1/4" pipe that will extend to at least 3" above bottom of

tank when screwed into tank adapter and tank adapter is
screwed into 2" coupling.

4. Screw this pipe into tank adapter, then screw tank adapter into

2" coupling.

5.  Mount pump on tank adapter.

ISLAND INSTALLATION

1. Install tank and piping per illustration.
2. The threaded 1-1/4" suction pipe is to extend 32-1/2" above

island.

3. Remove coupler from pedestal pipe by loosening set screws.
4. Slip pedestal pipe/pump base assembly over suction pipe.
5. Loosen screws in pump base to allow pedestal pipe to slide

down exposing end of suction pipe.

6. Screw coupler onto suction pipe.
7. Slide pedestal pipe into coupler, tighten set screws. Tighten

screws in pump base.

8. Mount pump on coupler.

ELECTRICAL

Pump motor voltage is factory set at 115 VAC. See diagram to
change voltage setting.
1. Install pump. Read and understand all the electrical wiring

instructions before proceeding.

2. Remove pump's electrical junction box cover and straighten the

wires to make the stripped wire ends accessible outside of the
junction box.

WARNING: AUX. WIRE IS LIVE WIRE!

  The AUX. lead wire is

insulated and enclosed when shipped. 

 Do not

 connect this wire

without first verifying the '

ON

' line voltage of the wire for

compatibility to the equipment to be installed.  Maximum amperage
on wire is 1 ampere.  The wire must be insulated and enclosed in
the junction box if not used.

3. Power to the unit should be supplied from a dedicated 30 amp

circuit breaker. No other equipment should be powered from this
breaker. Threaded rigid conduit, seal fittings and conductor seal
should be used. Provisions must be made to break both legs of
any AC circuit. Connect like colored pump wires to supply wires.
Ground wire must be connected.

4. Fold wires into junction box and replace cover making sure that

gasket is in place. Make sure screws are seated so there is no
space between the cover and the junction box.

TROUBLESHOOTING

IF PUMP FAILS TO PRIME: 

Check suction line for leaks or

obstructions.
Check bypass valve for dirt. The bypass poppet should slide
freely.

PUMP WILL NOT START: 

If motor hums but will not start, a

probable cause is a stuck rotor. Remove rotor cover; check rotor
and vanes for dirt. Also have an electrician check the electrical
power to the pump.

LOW PUMPING CAPACITY: 

Strainer screen clogged; bypass

valve not seated properly; obstruction in suction lines. Make sure
all 8 vanes slide easily in the rotor slots.

Содержание 300V Series

Страница 1: ...icable 2 Remove nozzle from nozzle boot and move switch lever up This will turn the pump on 3 Insert nozzle into container to be filled To minimize static electricity buildup keep nozzle in contact with container 4 Operate nozzle lever to dispense fluid 5 When desired amount of fluid has been dispensed release nozzle lever remove nozzle from container move switch lever to down position to turn off...

Страница 2: ......

Страница 3: ......

Страница 4: ...runs slowly 1 Incorrect voltage Check incoming line voltage while pump is running 2 Vanes sticking Check vanes and slots for nicks burrs and wear 3 Wiring problem Check for loose connections 4 Motor problem Return to place of purchase Motor stalls 1 Bypass valve sticking Remove and inspect valve must move freely be free of debris 2 Low voltage Check incoming line voltage while pump is running 3 Ex...

Страница 5: ... top of tank if the tank adapter is not used Use reducer bushings as required Fill Rite recommends using the vacuum breaker tank adapter with a 1 4 npt opening in the side of the hex portion that terminates in the vapor space of the tank Install tank adapter per instructions found in this manual Make liquid tight connection from the adapter to the vacu um breaker using a minimum of 1 4 metal tubin...

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ...la bomba la manguera la boquilla y el filtro para ver si hay bloqueo Reduzca la distancia vertical y horizontal de la bomba al líquido Retire la boquilla automática Limpie la cavidad de la bomba Regrese la unidad a donde la compró Elimine todos los desperdicios y reemplace la chaveta Extraiga y limpie la malla del filtro Revise la línea de aspiración para verificar si hay fugas o restricciones pue...

Страница 10: ...entubado debe tener una pendiente continua desde la bomba hasta el tanque Si la bomba está instalada debajo de la parte superior del tanque el entubado puede tener pendiente hacia ambos lados a partir de un único punto alto que esté encima del tanque Como alternativa el entubado puede canalizarse hasta cualquier abertura disponible sobre el tanque si no se utiliza el adaptador para tanque Utilice ...

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ...rotor des traces d usure excessive ou de dommages Vérifier sortie de pompe tuyau buse et filtre pour déceler un bouchage Réduire la distance verticale et horizontale de la pompe au liquide enlever la buse automatique Nettoyer la cavité de pompe Renvoyer au point d achat Éliminer tous les débris et remplacer la clé Sortir et nettoyer le tamis Chercher fuites ou restrictions dans la conduite d aspir...

Страница 15: ... la pompe est installée plus bas que le haut du réservoir le tube doit retomber de chaque côté à partir d un point haut situé au dessus du réservoir Comme alternative le tube peut également être amené sur n importe quelle ouverture en haut du réservoir si l adaptateur de réservoir n est pas utilisé Utiliser si nécessaire des bagues de rac cord d adaptation Fill Rite recommande d utiliser l adaptat...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ...rig Tank füllen Pumpe läuft langsam 1 Falsche Spannung Versorgungsspannung bei laufender Pumpe kontrollieren 2 Flügel klemmen Flügel und Nuten auf Kerben Grate und Verschleiß kontrollieren 3 Verdrahtungsproblem Auf lockere Anschlüsse kontrollieren 4 Motorproblem Zum Händler zurückbringen Motor wird abgewürgt 1 Umgehungsventil klemmt Ventil ausbauen und kontrollieren es muss sich frei bewegen lasse...

Страница 20: ... sich in der Rohrleitung keine Flüssigkeitsfallen befinden Die Rohrleitung muss ein kontinuierliches Gefälle von der Pumpe bis zum Tank aufweisen Wenn die Pumpe unterhalb der Tankoberseite des Tanks montiert ist kann das Rohr ein Gefälle in beide Richtungen von einem einzigen hohen Punkt über dem Tank aufweisen Wahlweise kann die Rohrleitung zu einer vorhandenen Öffnung auf der Tankoberseite gefüh...

Отзывы: