Explosion-Proof Transmitter and Controller Instruction Manual
55
Scaling the 4-20 mA Analog Output (
Aout
)
The 4-20 mA analog outputs can be scaled to provide a 4-20 mA signal for any display range selected. The
Analog Outputs can be mapped to PVs or Math Channels. To select the channel and source assignments
the analog outputs are assigned to, see
Analog Output Source Programming
on page 70.
No equipment is needed to scale the analog outputs; simply program the display values to the
corresponding mA output signal.
The
Analog Output
menu is used to program the 4-20 mA outputs based on display values.
There are three analog outputs available. These only display when they are enabled. See graphic below.
Notes: Changes to the settings are saved to memory only after pressing ENTER. Changes made to settings
prior to pressing ENTER are not saved. Once ENTER is pressed, the display moves to the next menu.
*
*
* If Installed