![turck TX715FB-P3CV01 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/turck/tx715fb-p3cv01/tx715fb-p3cv01_quick-start-manual_1181794003.webp)
TX715FB-P3CV01
HMI – TX715FB-P3CV01
Other documents
The following additional documents are available online at
www.turck.com
■
Data sheet
■
Instructions for use for TX series
■
EU declaration of conformity (current version)
For your safety
Intended use
The HMIs (Human Machine Interfaces) of the TX700 family are used to control,
operate and monitor machine processes.
The HMI/PLC operator panels of the F&B series are suitable for use in the F&B
industry and comply with the standards and guidelines for hygienic design
DIN EN1672-2 and EHEDG/FDA 21 CFR 177.2006.The devices may only be used
as described in this manual.
Any other use is not in accordance with the intended use. Turck accepts no li-
ability for any resulting damage.
General safety instructions
■
The device may only be assembled, installed, operated, parameterized and
maintained by professionally-trained personnel.
■
The device only meets the EMC requirements for industrial areas and is not
suitable for use in residential areas.
■
The devices may only be used in accordance with applicable national and
international regulations, standards and laws.
■
Do not open the devices under voltage.
Product description
Device overview
See fig. 1
Functions and operating modes
The devices of the TX700 series combine control, operation and monitoring
by a CODESYS V3 PLC with web visualization to a complete control unit. The
CODESYS V3 control of the TX700 devices has the functions PROFINET controller,
EtherNet/IP scanner and Modbus TCP as well as Modbus RTU master. Addi-
tionally the devices of the TX700 family can be used as Modbus TCP as well as
Modbus RTU slave.
Additional functions
■
Ethernet TCP/IP or UDP/IP communication
■
OPC-UA server and client, MQTT
■
Serial communication via RS232, RS485 and RS422
Installing
See fig. 2 and 3
A = TX7…
B = installation cut-out
➤
Screw each fixing screw until the bezel corner gets in contact with the panel.
The maximum tightening torque is 1.3 Nm.
➤
Do not cover the ventilation slits in the device.
TX…
Brackets included in delivery
TX715FB
12
Connecting
Connectors and slots
See fig. 4
Connector/slot
Function
1
USB port , V2.0, max. 500 mA (for maintenance only)
2
Ethernet port 2 (10/100 Mbit)
3
Ethernet port 1 (10/100 Mbit)
4
Serial interface
5
Ethernet port 0 (10/100/1000 Mbit)
6
Power supply
7
SD card slot
8
2 expansion slots for plug-in modules
NOTE
Devices of protection class III according to EN 61140 or Class 2 according to UL
standards: All connections are SELV connections.
Power supply
➤
Connect the device to the voltage supply according to fig. 5 and 6.
DANGER
Wrong selection of power supply
Danger to life due to overvoltage and electric shock!
➤
Only operate devices at SELV power supplies.
Grounding the device
The minimum conductor cross-section for the ground connection is 1.5 mm².
➤
Ground the housing via the grounding screw on the back of the housing.
➤
Connect terminal 3 on the power supply terminal block to ground.
Serial interface
See fig. 7
Pin
RS232
RS422/RS485
1
RxD
CHB-
2
TxD
CHA-
3
CTS
CHB+
4
RTS
CHA+
5
+5 VDC output
+5 VDC output
6
GND
GND
7
n. c.
n. c.
8
Shield
Shield
NOTE
When used as RS485 interface, pins 1 and 2 as well as pins 3 and 4 must be
connected externally.
Maintenance
➤
Clean the devices at regular intervals with a damp cloth.
Repair
The device must not be repaired by the user. The device must be decommis-
sioned if it is faulty. Observe our return acceptance conditions when returning
the device to Turck.
Disposal
The device is equipped with a rechargeable lithium battery, which is not user
replaceable.
➤
For disposal, open the back of the device and remove the battery.
The device and the lithium battery must be disposed of properly in ac-
cordance with WEEE Directive 2012/19/EU and must not be included in
general household garbage.
EN
Quick Start Guide
© Hans Turck GmbH & Co. KG | 1000015594 2020-11 DE EN FR