EN

Quick Start Guide

TX-CAN – CAN-master Plug-in I/O module

Description 

The communication module is an interface designed to connect the operator 
panel connect to the CAN network. The connection to the CAN network is real-
ized via the dedicated DB9 male connector. 

Communication protocol 

CAN 2.0 

Max. transmission speeds 

1 Mbit

Galvanic insulation   

Yes, optical

CAN-interface

See fig. 1

Pin assignment/connector view

Pin

Description

1

n.c.

2

CAN_L

3

GND

4

n.c.

5

n.c.

6

n.c.

7

CAN_H

8

n.c.

9

n.c.

Dimensions

See fig. 2

Mounting/unmounting

Remove the protective cover from the connector before installing the module 
and mount  the module according to fig. 3.

ATTENTION

Risk of short circuits

Destruction of electronic circuits!

Do not connect or disconnect when energized.

Approvals and standards

The products have been designed for use in Hazardous Location according 
ANSI/ISA-12.12.01.
These products have been designed for use in combination with the HMIs of 
the  TX500 product family in an industrial environment in compliance with the 
2014/30/EU

 

directive.

Compliance

The products have been designed in compliance with:

 

EN 61000-6-1 to -6-4

 

EN 61000-4-2 to -4-6, EN 61000-4-8

 

EN 55011, Class A

 

EN 60945

ATTENTION

Operation in r

esidential and commercial areas

Electromagnetic disturbances!

In case of the operation of the devices in residential and commercial areas, 

observe the measurement values according to IEC-61000- 6-3.

Safety notes for the operation in hazardous areas (only approved in 
USA and Canada, no ATEX Certification!) 

NOTE

The  Power, input and output (I/O) wiring has to be done in accordance with  

Class I, Division 2 and in accordance with the authority having jurisdictions. For 

U.S. in accordance with  Article 501.10 (B) of the National Electrical Code, NFPA 

70 and for Canada in accordance with  Section 18-1J2 of Canadian Electrical 

Code.  

DANGER

Loss of Class 1, Division 2 approval in case of substitution of components

Danger to life due to risk of explosion!

Do not use components which do not comply with the Class 1, Division 2 

certification.

DANGER

Replacing or wiring modules under voltage

Danger to life due to risk of explosion!

Switch-off the device before replacing or wiring modules.

DANGER

Disconnecting devices under voltage

Danger to life due to risk of explosion!

Do not disconnect devices under voltage, as long as they are installed in 

ignitable atmospheres.

NOTE

The devices are suitable for the use in Class 1, Division 2, groups A, B, C and D 

(hazardous locations and non-hazardous locations).

DANGER

Replacing the battery

Danger to life due to risk of explosion!

Do not replace the battery as long as they are installed in ignitable atmo-

spheres.

© Hans Turck GmbH & Co. KG | D301405 2016-06 DE EN FR 