V02.00 | 2019/10
119
9.1.1
Adapting process data mapping
The mapping of process data can be adapted application-specifically via the IO-Link master's
parameterization.
Depending on the used fieldbus, it can be necessary to swap process data word-wise, double
word-wise or completely in order to align them to the data structure in the PLC. The process
data mapping is determined channel by channel through the parameters
process input data
mapping
and
process output data mapping
.
Example mapping for field buses with Little Endian-format:
Mapping through the IO-Link master
Ò
field bus
Ò
PLC
Byte
Device at
IO-Link port
Device process data in
IO-Link master
Parameter:
Process data
mapping
Device process data to field bus
Byte 0
Status
Status
Byte 1
Control
Control
IO-Link port 1
Byte 2
Temperature
sensor TS…
Temperature
Low byte
swap 16 bit
Temperature
High byte
Byte 3
High byte
Low byte
IO-Link port 2
Byte 4
Linearity sensor
Li…
Position
Low byte
swap 16 bit
position
High byte
Byte 5
High byte
Low byte
IO-Link port 3
Byte 6
I/O hub TBIL-…
Digital
signals
0…7
Direct
Digital signal
0…7
Byte 7
Digital
signals
8…15
Digital signal
8…15
IO-Link port 4
Byte 8
Diagnostics
swap all
Counter/position
value
Most
Significant
Byte
Byte 9
Rotary encoder
RI…
Counter/position
value
Low byte
High byte
Byte 10
High byte
Low byte
Byte 11
Most
Significant
Byte
Diagnostics