EN
Quick Start Guide
PSU67-3P-1MP-2M5-24200-F
Other documents
The following additional documents are available online at
www.turck.com
:
■
Data sheet
■
EU declaration of conformity (current version)
For your safety
Intended use
The power supply unit PSU67-3P-1MP-2M5-24200-F is a stand-alone power
supply for three-phase mains systems for indoor use.
The devices must only be used as described in these instructions. Any other
use is not in accordance with the intended use. Turck accepts no liability for
any resulting damage.
General safety instructions
■
The device must only be mounted, installed, operated and maintained by
trained and qualified personnel.
■
The device is a ”Class of Protection I” equipment according to IEC 61140.
■
The device is designed for pollution degree 3 areas in controlled environ-
ments.
■
Do not use the device without additional protective devices in the area of
personal and machine protection.
■
Operate the device exclusively within the technical specifications.
■
Do not connect the negative potential of any output externally to PE.
■
Do not use without a proper PE (Protective Earth) connection.
Product description
Device overview
S. fig. 2: dimensions, s. fig. 3: block diagram
Functions and operating modes
The power supply provides a stabilized and galvanically separated PELV
output voltage at the two outputs OUT1 and OUT2. The negative potential of
the outputs is permanently connected to PE within the unit.
The output is electronically protected against no-load, overload and short
circuit and can supply any kind of loads, including unlimited inductive and
capacitive loads.
If capacitors with a capacitance >20 mF are connected to one output, this
output might switch off after turning the unit or the output on or connect-
ing the load.
The device is equipped with an over-temperature protection. In case of an
over temperature, the device shuts down and starts automatically again
after cooling off.
In case of an internal defect, a redundant circuit limits the maximum output
voltage to 32.5 V. The outputs are shut down and restart automatically if the
defect is eliminated.
Mounting
General installation instructions
The enclosure of the device provides a degree of ingress protection of IP65
and IP67 when installed with all mating connectors firmly connected.
The device is generally designed for altitudes up to 5000 m (16400 ft). Above
2000 m (6560 ft), output current and overvoltage category must be reduced.
When using the device in TN, TT and IT networks the following applies:
■
TN, TT mains systems with earthed neutral and IT star mains systems with
insulation monitoring: Use in zones of overvoltage category III up to an
altitude of 2000 m (6560 ft), use in zones of overvoltage category II up to
an altitude of 5000 m (16400 ft)
■
TN, TT, IT delta mains systems or IT star mains systems without insulation
monitoring: Use in zones of overvoltage category II up to 2000 m (6560 ft)
The device uses convection cooling. An external fan is not necessary.
Mounting instructions
CAUTION
Sharp edges on the back of the device
Risk of injury
➤
Mount the devices on a sufficiently large, even surface so that all sharp
edges are covered.
➤
Mount the device vertically with the connection level facing downwards
on a flat surface using two screws each at the upper and lower mounting
holes.
➤
Other mounting orientations: reduce the output current.
➤
Do not obstruct airflow. Do not cover ventilation fins.
➤
Observe the minimum installation clearances: 50 mm on top and bottom,
10 mm on the front and 10 mm left and right side.
Connection
➤
Connect the device according to “Wiring diagrams”.
Mating connectors
■
Input voltage (XD1): 7/8” male connector, 4 pole, multi coded
■
Relay OK signal (X0): standard M12 female connector, 5 pole A coded
■
Output voltage (XD2, XD3): 7/8“ male connector, 5-pole
Suitable accessories can be found in the Turck product database at
www.turck.com
. The accessories are not part of the scope of delivery.
➤
Do not apply return voltages from the load to the outputs higher than
35 V.
➤
Do not connect outputs or devices in parallel for higher output currents.
© Hans Turck GmbH & Co. KG | 100029123 2021-04 DE EN
PSU67-3P-1MP-2M5-24200-F
PSU67-3P-1MP-2M5-24200-F
IP67 Power Supply
Quick Start Guide
Doc-No. 100029123 2104
Additional
information see
180.6 [7.11"]
183.0 [7.20"]
90%
80%
60%
50%
200%
175%
Voltage
Set
OUT 1
150%
125%
100%
70%
Status
20%
OUT 2
38.0 [1.50"]
107.0 [4.21"]
58.7 [2.31"] REF
40.0 [1.57"]
80.0 [3.15"]
111.0 [4.37"]
turck.com