background image

Your Global Automation Partner

Instructions for Use

PS310… | PS510…

Pressure Sensors

Содержание PS310 Series

Страница 1: ...Your Global Automation Partner Instructions for Use PS310 PS510 Pressure Sensors...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...ctions and operating modes 10 4 5 1 Setting options 10 4 5 2 Normal operation Run mode 10 4 5 3 Menu mode 10 4 5 4 Programming mode 10 4 5 5 Output functions Switching output 11 4 5 6 Output functions...

Страница 4: ...nts 4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 10 Troubleshooting 27 11 Maintenance 28 12 Repair 28 12 1 Returning devices 28 13 Disposal 28 14 Technical Da...

Страница 5: ...on with medium risk of death or severe in jury if not avoided CAUTION CAUTION indicates a dangerous situation of medium risk which may result in minor or moderate injury if not avoided NOTICE NOTICE i...

Страница 6: ...A 0 16 bar absolute 25V 1 25 bar 25A 0 25 bar absolute 40V 1 40 bar 100 0 100 bar 250 0 250 bar 400 0 400 bar 600 0 600 bar 03 Mechanical version Mechanical version 01 G1 4 female thread 02 1 4 18NPT...

Страница 7: ...The Turck product database contains software tools for programming configuration or commissioning data sheets and CAD files in numerous export formats You can access the product database at the follo...

Страница 8: ...ow the measured values in a display The sensors are vacuum tight The devices may only be used as described in these instructions Any other use is not in accord ance with the intended use Turck accepts...

Страница 9: ...r one analog output adjustable as current or voltage output 4 1 Device overview 24 91 5 3 60 38 1 50 Electrical Connection Process Connection L 55 1 2 17 12 2 0 48 Fig 1 Dimensions in mm inch 4 2 Prop...

Страница 10: ...be set via IO Link and with the touchpads A window function and a hysteresis function can be set for the switching outputs The measuring range of the analog output can be defined as required The meas...

Страница 11: ...lue is changed the lower limit value is automatically adjusted P FH 1 FL t 0 1 0 Fno Fnc Gutbereich acceptable range Fig 2 Behavior of the switching output window function Hysteresis function The hyst...

Страница 12: ...ent output 4 20 mA Fig 5 Behavior of the current output 0 20 mA Voltage output In the defined measuring range between ASP analog start point and AEP analog end point the output signal is between 0 and...

Страница 13: ...length 2 m sheathing material PUR black cULus ap proval 26 5 M12 x 1 15 32 14 L 50 5 USB 2 IOL 0002 IO Link adapter with integ rated USB interface 41 24 54 M12 x 1 16 USB Mini IN DC LED CH1 C Q CH2 D...

Страница 14: ...as shown in the figure Note the different pressure connections Mount the sensor in any direction The display of the unit can be rotated by 180 The maximum tightening torque for fastening the sensor i...

Страница 15: ...ct the open end of the connection cable to the power supply and or processing units 6 1 Wiring diagrams 3 2 4 1 1 L 3 L 2 out 2 switch 4 out 1 switch IO Link Fig 10 Pin layout PS 2UPN Fig 11 Wiring di...

Страница 16: ...Commissioning 16 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 7 Commissioning The device is operational automatically once the power supply is switched on...

Страница 17: ...s active Off Device unlocked 8 2 Display indications Display Meaning Flashing Measured value out of analog range OL Value outside of the measuring range pressure more than 5 of full scale above the li...

Страница 18: ...8 3 Display indications Diagnostic messages Display Meaning ErrP Error in measuring cell ErrC Communication error ErrA Ambient pressure error SC1 Short circuit at output 1 SC2 Short circuit at output...

Страница 19: ...ting The device can be assigned parameters as follows n Setting via touchpad n Setting via IO Link The following flow charts illustrate the operating steps during the teach in process Fig 16 Overview...

Страница 20: ...Setting 20 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com Fig 17 Overview of the teach EF menu...

Страница 21: ...V01 00 2020 01 21 Fig 18 Overview of the menu navigation...

Страница 22: ...MODE and SET for 3 s a LOC flashes first and then is permanently lit yellow The sensor is automatically locked if the touchpads of the sensor are not actuated for 1 min 9 1 3 Setting parameter values...

Страница 23: ...is function ou1 Hno Hnc Upper limit value at which output 1 changes its switching state when the pressure increases rP1 Reset switching point 1 for hysteresis function ou1 Hno Hnc Lower limit value at...

Страница 24: ...u2 Auto analogvalues rtio Pressure value at which the analog signal has its start point AEP End point of the analog signal ou2 Auto analogvalues rtio Pressure value at which the analog signal has its...

Страница 25: ...frequency pressure peaks can be filtered 0 8 s in increments of 0 01 s 0 filter is deactivated dAA Damping of the analog output Filter for momentary or high frequency pres sure peaks 0 8 s in incremen...

Страница 26: ...tions see data sheet via the IO Link communication interface both offline e g with the configuration tool as well as also on line via the controller An overview of the different functions and properti...

Страница 27: ...irst check whether ambient interference is present If there is no ambient interference present check the connections of the device for faults If there are no faults there is a device malfunction In th...

Страница 28: ...ned if it is faulty Observe our return acceptance conditions when returning the device to Turck 12 1 Returning devices Returns to Turck can only be accepted if the device has been equipped with a Deco...

Страница 29: ...Switching frequency Operating voltage 18 33 VDC Temperature of medium 40 90 C Ambient temperatur 40 80 C Storage temperature 40 100 C TK Zero point 10K Range 10K Voltage drop at Ie Burst protection Se...

Страница 30: ...de PS 310 PS 510 Housing nut with tightening torque 35 Nm Rotatable display Yes Sensor body adjustable Yes Vibration resistance 20 g 10 2000 Hz acc to EN 60068 2 6 Shock resistance 50 x g 11 ms acc to...

Страница 31: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100004407 2020 01 100004407...