Setting
Setting via teach adapter RP-Q21
24
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9
Setting
The devices have an adjustable analog output. The measuring range can be set by manual
bridging or with the RP-Q21 teach adapter. The zero point and end point of the measuring
range can be set in succession or independently of one another.
9.1
Setting via manual bridging
Supply the device with voltage.
Place positioning element at the zero point of the measuring range.
Bridge pin 2 and pin 3 for 4 s.
Interrupt bridge between pin 2 and pin 3 for 1 s.
a
Sensor starts teach mode.
Bridge pin 2 and pin 3 within 5 s.
a
The zero point of the measuring range is stored.
Place positioning element at end point of the measuring range.
Bridge pin 2 and pin 3 for 4 s.
Sensor starts teach mode.
Interrupt bridge between pin 2 and pin 3 for 1 s.
Bridge pin 1 and pin 2 within 5 s.
a
The end point of the measuring range is stored.
9.2
Setting via teach adapter RP-Q21
Connect the sensor to the teach adapter.
Place positioning element at the zero point of the measuring range.
Press the Zero button of the teach adapter for 4 s.
Release the Zero button of the teach adapter for 1 s.
a
Sensor starts teach mode.
Press the Zero button of the teach adapter again within 5 s.
a
The zero point of the measuring range is stored.
Place positioning element at end point of the measuring range.
Press the Zero button of the teach adapter for 4 s.
Release the Zero button of the teach adapter for 1 s.
a
Sensor starts teach mode.
Press the Span button of the teach adapter again within 5 s.
a
The end point of the measuring range is stored.