IO-Link Parameters – IO-Link Version 1.1

LRS510…-2UPN8…

Radar Level Sensor

Содержание LRS510 Serius

Страница 1: ...Your Global Automation Partner IO Link Parameters IO Link Version 1 1 LRS510 2UPN8 Radar Level Sensor...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...cuments 5 1 4 Feedback about these instructions 5 2 Notes on the Product 6 2 1 Product identification 6 2 2 Manufacturer and service 6 3 Software Supported IO Link Parameterization 7 4 IO Link Paramet...

Страница 4: ...Contents 4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 5: ...on of medium risk which may result in minor or moderate injury if not avoided NOTICE NOTICE indicates a situation which may lead to property damage if not avoided NOTE NOTE indicates tips recommendati...

Страница 6: ...der Ruhr Germany Turck supports you with your projects from initial analysis to the commissioning of your applic ation The Turck product database contains software tools for programming configuration...

Страница 7: ...ting the parameters via IO Link n via on request data objects e g close to the PLC via IO Link function block n via tool based engineering via FDT DTM e g PACTware with the use of DTM or the IODD Devi...

Страница 8: ...Parameters 4 1 General parameters Parameter Content Vendor ID 317 0x13D Device ID 524289 0x80001 IO Link version 1 1 Bitrate COM2 38 4 kbit s Minimum cycle time 5 ms SIO supported True M Sequence Cap...

Страница 9: ...ss data 0 4 28 False Integer 19999999 134217727 134217721 Measurement value is filtered 134217722 Sensor muted 134217723 Value underrun 134217724 Value overrun 134217725 Geometry error 134217726 No ta...

Страница 10: ...ger 0 253 System command 128 Device Reset 129 Application Reset 130 Restore Factory Settings The VDMA Turck menu selection is not reset 160 Reset lowest recorded level 161 Reset highest recorded level...

Страница 11: ...dware Version 0x16 22 0x0 0 True read 0 0 512 String Hardware revision Firmware Version 0x17 23 0x0 0 True read 0 0 512 String Firmware revision Application Specific Tag 0x18 24 0x0 0 True read write...

Страница 12: ...0x0 0 True read write 0 0 32 UInteger NaN NaN 10000 00 Operating hours alert limit Switching counter limit 0x4B 75 0x0 0 True read write 0 0 32 UInteger NaN NaN 10000 00000 Alert limit for number of...

Страница 13: ...rate 0x55 85 0x0 0 True read write 0 0 8 UInteger 0 3 0 Display update period 0 50 ms 1 200 ms 2 600 ms 3 Display off Output 1 Errorstate 0x56 86 0x0 0 True read write 0 0 8 UInteger 0 1 0 State of ou...

Страница 14: ...True read write 0 0 8 UInteger 0 1 0 Rotate the display to be readable from above 0 0 1 180 SP FH Output 1 0x60 96 0x1 1 False read write 0 0 28 Integer 1999 9999 99999 999 0 Measured value 10000 Valu...

Страница 15: ...rrun 13421 7725 Geometry error 13421 7726 No target detected 13421 7727 Internal Error Damping switching 0x71 113 0x0 0 True read write 0 0 16 UInteger 0 800 0 Risetime and falltime 0 90 of analog out...

Страница 16: ...0 Flat ends 1 Dished bottoms at both ends Lowest filling level 0x88 136 0x4 4 False read write 6 0 28 Integer 1999 9999 99999 999 0 Highest filling level 0x88 136 0x5 5 False read write 10 0 28 Integ...

Страница 17: ...d 1 Unit displayed for 1 s after 4 s value Custom geometry height nodes 0x8B 139 0x0 0 False read write 0 0 512 Array 0 13421 7724 13421 7723 Value underrun 13421 7724 Value overrun Custom geometry vo...

Страница 18: ...suppression 0x95 149 0x0 0 True read write 0 0 16 UInteger 1750 50250 50250 Signals behind this distance limit are ignored IO Link Index 0xA8 168 0x1 1 True read 0 0 16 UInteger 0 149 0 Block transfer...

Страница 19: ...o error 1 Display brightness is to low 2 Display brightness is to high 3 Unknown display update rate 4 Unknown display rotation setting 5 Unknown display color setting 6 Unknown value in the entry whe...

Страница 20: ...range 91 Highest filling level is outside of detection range 92 The distance between highest and lowest filling level is to small 93 Tank diameter is smaller than highest filling level 95 Tank length...

Страница 21: ...maximum filter value 129 Maximum value for signal amplitude filter is to small 130 Maximum value for signal amplitude filter is to large 131 Maximum value for signal amplitude filter is to close the...

Страница 22: ...olerance 30480 Error Short circuit Check installation 35856 Warning Process variable range over run Process data uncertain 35888 Warning Process variable range under run Process data uncertain 36001 E...