D301171 - IO-Link master 1108
4-7
Application example with Siemens PLC and FB 102 (IO-Link CALL)
4
For the meaning of the parameters (IO-Link, index 1, subindex x), please read the
documentation for the respective sensor
”Extract from the documentation of the
.
SIO mode
If the port has to be operated in SIO mode, please select devices with 0 byte of process
data [TURCK … (SIO mode) or Generic 0 Byte (SIO mode)] from the hardware catalog.
Configuration of the IO-Link ports in this example
1
A TURCK pressure sensor (PS100R-501-LI2UPN8X-H1141) is connected to IO-Link port 1
(slot 2) which has to be operated in IO-Link mode.
The default-entry "Generic In 8 Byte" at slot 2 is therefore replaced by the sensor Turck
PS series (IOL mode) from the hardware catalog.
Parameterization of the TURCK-sensors
The TURCK sensor is parameterized according to the application as shown for example in
. A description of the sensor-parameters can be found
in the respective sensor-documentation under
www.turck.com
.
2
A Siemens ultra sonic sensor, PXS310C M18 IO-Link (6GR6333-3KS00) is connected to
IO-Link port 3 (slot 4). It should also be used in IO-Link mode.
The sensor is not part of the GSD-file of the TURCK IO-Link master and can therefore only
be inserted as generic sensor (see
“Configuration of the IO-Link ports“
). According to the
vendor, it has 2 byte of process data.
Figure 17:
Parameteriza-
tion via GSD
Содержание IO-LINK MASTER
Страница 1: ...IO LINK MASTER User Manual...
Страница 7: ...D301171 IO Link master 1108 iv...
Страница 65: ...Connection to a Siemens Step 7 usage of the TURCK example program D301171 IO Link master 1108 4 16...
Страница 75: ...Acyclic data exchange via PROFIBUS DP C2 master and TURCK IO Link DTM D301171 IO Link master 1108 5 10...
Страница 83: ...Guidelines for electrical installation D301171 IO Link master 1108 6 8...
Страница 85: ...Index D301171 IO Link master 1108 7 2...