Product Description
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
4.1.2
Safety Function IM12-CD01-2R-1U
SIL2 – Loop Powered mode with one channel
SIL2
[E1]
[A1]
Safety Function:
If a Low signal is present at input [E1], the corresponding output relay (A1) is de-energized within maxi-
mum 40 ms, so that NO contact is open and NC contact is closed.
NE load connection:
Safety Function for NE (Normally Energized) load (de-energized in safe state) is available at Terminal
Blocks 7…8 [A1].
ND load connection:
Safety Function for ND (Normally De-Energized) load is available at Terminal Blocks 6…8 [A1].
SIL3 – Loop Powered mode with 1oo2 channel architecture
SIL3
[E1]
[A1+A2]
NE load
Safety Function:
If a low signal is present at input [E1], connected by a single SIL3 signal source, the output relay [A1] and
[A2] are de-energized within maximum 40 ms, so in serial connected NO contacts are open
NE load connection:
SIL 3 Safety Function for NE (Normally Energized) load (de-energized in safe state) is available at Termi-
nal Blocks 7…4. Two NO contacts in series connection.
7
6
8
YE
9
10
3
5
4
YE
A1
(SIL 2)
E1
NC
NO
COM
NC
NO
COM
7
6
8
YE
9
10
3
5
4
YE
A1
(SIL 3)
E1
NC
NO
COM
NC
NO
COM
Содержание IM12-CD
Страница 1: ...Your Global Automation Partner IMX12 CD IM12 CD Relay Coupler Safety Manual...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 4: ...4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 22: ...www turck com Over 30 subsidiaries and over 60 representations worldwide 100004636 2019 04 100004636...