Implementation of EtherNet/IP™
D301271 1013 - FGEN - multi protocol
7-26
7.3.6
Ethernet Link Object (0×F6)
The following description of the Ethernet Link Object is taken from the CIP specification, Vol. 2, Rev. 1.1
by ODVA & ControlNet International Ltd. and adapted to FGEN.
Class Attributes
Instance attributes
Table 7-17:
Class Attributes
Attr. No.
Attribute name
G
et/
S
et
Type
Value
1 (0×01)
REVISION
G
UINT
1
2 (0×02)
MAX OBJECT INSTANCE
G
UINT
1
3 (0×03)
NUMBER OF INSTANCES
G
UINT
1
6 (0×06)
MAX CLASS IDENTIFIER
G
UINT
7
7 (0×07)
MAX INSTANCE ATTRIBUTE
G
UINT
6
Table 7-18:
Instance
attributes
Attr. No.
Attribute name
G
et/
S
et
Type
Description
1 (0×01)
INTERFACE SPEED
G
UDINT
Speed in megabits per second
(e.g., 10, 100, 1000, etc.)
2 (0×02)
INTERFACE FLAGS
G
DWORD
see
3 (0×03)
PHYSICAL
ADDRESS
G
ARRAY OF
USINT
Contains the interface’s MAC address
(TURCK: 00:07:46:××:××:××)
6 (0×06)
INTERFACE
CONTROL
2 WORD
Allows port-wise changes of the Ethernet-
settings
7 (0×07)
INTERFACE TYPE
10 (0×0A)
INTERFACE LABEL
Table 7-19:
Interface flags
Bits
Name
Definition
Default value
0
Link Status
Indicates whether or not the Ethernet
802.3 communications interface is
connected to an active network.
0 = inactive link
1 = active link.
Depends on
application
1
Half / Full Duplex
0 = half duplex;
1 = full duplex
If the Link Status flag is 0, the value of the
Half/Full Duplex flag is indeterminate.
Depends on
application
Содержание FGEN-AIM Series
Страница 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Страница 8: ...D301271 1013 FGEN multi protocol vi...
Страница 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Страница 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Страница 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Страница 104: ...Application example FGEN for EtherNet IP with Allen Bradley PLC and RS Logix 5000 D301271 1013 FGEN multi protocol 8 14...
Страница 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Страница 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...