Hardware description
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
22
3.6.5
Address setting via the mode PGM-DHCP (universal mode)
In order to activate the PGM-DHCP-mode, the DIP-switch MODE is set to "ON", the rotary switches
to address "60" (see
Device addressing and operation mode setting (page 19)
The device sends DHCP-requests until an IP address is assigned (DHCP-server, PROFINET-controller,
PACTware™, web server, IP-Address Tool).
The assigned IP-address is stored to the device and the DHCP-client is stopped.
Even after a restart of the device, the device sends no further DHCP-requests.
PGM-DHCP in PROFINET
This mode assures a PROFINET-compliant operation of the modules.
NOTE
After every change of the address-mode, a voltage reset must be done.
NOTE
If a DHCP-server is used within the network, problems may occur during IP-assignment.
In this case, both, the DHCP-server as well as the PROFINET-controller (via DCP), try an IP-
address-assignment.